1 建设项目概况 ··········································································· 3 1.1建设项目内部基本情况 ···························································· 3 1.2建设项目外部基本情况 ···························································· 5 2 建设项目涉及的危险、有害因素和危险、有害程度 ··············· 8 2.1危险、有害因素········································································ 8 2.2危险、有害程度······································································ 13 3 建设项目设立安全评价报告中的安全对策和建设采纳情况说明 ·· 17 4 采用的安全设施和措施 ·························································· 18 4.1项目选址、平面布置和建筑结构的安全措施 ························· 18 4.2工艺和设备的安全措施 ·························································· 19 4.3电气的安全措施······································································ 21 4.4消防的安全措施······································································ 21 4.5预防火灾与爆炸的对策措施 ··················································· 22 4.6重大危险源的安全措施 ·························································· 23 5 事故预防及应急救援措施······················································· 24 5.1应急救援组织或应急救援人员的设置或配备情况 ················· 24 5.2消防队伍的依托或者建设情况 ··············································· 24 5.3应急救援器材的配备情况 ······················································· 24 5.4消防器材的配备情况 ······························································ 24 5.5应急救援措施 ········································································· 24 6 安全管理机构的设置及人员配备 ··········································· 29

6.1劳动安全管理机构设置及人员配备 ········································ 29 7 安全设施投资概算 ·································································· 30 7.1建设项目总投资概算 ······························································ 30 7.2建设项目中安全设施投资概算和分类投资概算 ····················· 30 7.3安全设施投资概算占总投资概算的比例,安全设施分类投资 概算占安全设施投资概算的比例 ················································· 31 8 结论和建议 ············································································· 32 8.1结论 ························································································ 32 8.2建议 ························································································ 33

1 建设项目概况

1.1 建设项目内部基本情况

1.1.1 建设项目的主要技术、工艺

中国石油天然气股份有限公司湖北宜昌宜顺加油站参照《汽车加油加气站设计与施工规范》等标准、规范的要求,采用国内外通行的成品油流程及加油工艺。建设规模为二级加油站:拟建乙醇汽油储罐3个,柴油罐2个,容积均为30m3。

1.1.2 建设项目所在的地理位置、用地面积和生产(储存)规模

本项目拟建于宜昌市猇亭经济技术开发区,猇亭大道东段,即正大集团至亚元电子有限公司路段,面邻猇亭大道,距宜昌市中心城区约20公里,距葛洲坝水利工程约25公里,距三峡电站坝址66公里,近邻宜黄高速公路及黄龙寺机场。拟建站址南临宜顺机动车检测中心,北面与东面均为农田及山林,与周围民居住宅水平距离均在30米以上。(站址具体区域位置详见附件四:项目区域位置图。)

本项目总用地面积3992平方米,站场呈L形,分别布置有加油区、站房和储罐区。其中加油区面邻猇亭大道,中间以绿化带相隔。加油区主要由罩棚、加油岛和加油机组成,拟建加油岛4个、双枪加油机4台。储罐区布置于站区东北角,区内拟设置30m3油罐5个,其中乙醇汽油罐3个,柴油罐2个。站区北面为站房(二层楼房)、公共卫生间,站房内设办公室、发电与配电间、便利店、储藏室、员工休息室及餐厅等。加油站出入口沿猇亭大道呈南北方向布置,南进北出。该加油站总平面布置详见附件:总平面布置图。 1.1.3 建设项目涉及的主要原辅材料和品种名称、数量

本项目涉及的主要原辅材料和品种名称、数量见表1-1。

表1-1主要原料、中间体、产品的种类及数量

数 量 品 名 危 规 号 31001 32061 危险 类别 第3.1类低闪点易燃液体 第3.2类中闪点易燃液体 / 单位产品消耗量 (吨) / / / 贮存区 储存量(m3) 生产存储临界量(吨) 备注 汽油 乙醇 柴油 81 9 60 20 20 20 原料 原料 原料 / 1.1.4 建设项目的工艺流程和主要装置及其上下游生产装置的关系 1.1.4.1 工艺流程

本加油站采用国内外通行的成品油流程及加油工艺,即成品油从批发库经油罐车运输至加油站,通过卸油管将油品卸至埋地油罐。加油时,油品从埋地油罐经管道、自吸加油机、自封式加油枪给车辆加油。成品油流程及加油工艺流程图见附件一:附图1-1。

油库 → 油罐车 → 加油站 → 卸油 → 埋地油罐 → 油品管道 → 加油机 → 车辆 附图1-1: 加油工艺流程图

1.1.4.2 加油站主要装置及其上下游生产装置的关系

加油站主要建设内容包括:加油站房、加油站棚、油储罐、加油设备及与加油站配套的公用工程和辅助设施。 1.1.5 建设项目配套和辅助工程 1.1.5.1 给排水

本项目用水主要包括生活用水及消防用水,用水来源于城市自来水管网,完全可满足本项目的供水。

本项目排水主要为生活废水,废水直接排入城市下水管道。 1.1.5.2 供电、通讯

该加油站站区内设置一间配电间, 电源拟引自市电,电压380V/220V,配电箱拟设在站房配电间内,设计用电负荷为三级,可满足站内生产、生活使用。站内发电间拟配24KW发电机,供停电时使用。站区内设置有线和无线通讯系统。 1.1.5.3 消防及安全防护措施

1、消防设施

该加油站消防器材依据《汽车加油加气站设计与施工规范》的各项规定及建设方提供的相关资料进行配置。未设消防给水,着火时主要用站内配置的消防器材灭火。站房内按《建筑灭火器配置设计规范》相关规定放置灭火器。

2、 防静电及接地保护

地上及埋地管沟管路末端,设计作防静电和防感应雷的接地装置,接地电阻按不大于10欧姆设计,卸油车场地静电接地柱装置接地电阻按不大100欧姆设计。加油机亦接入静电接地网。工艺管线、法兰铜片跨接线,电阻按不大于0.03欧姆设计。管线拟采用40×4扁钢接地。 1.1.6 建设项目的主要装置名称、型号、材质、数量

本项目主要装置名称、型号、材质、数量见附件一:附表1-1。

1.2 建设项目外部基本情况

1.2.1 建设项目所在地的气象、水文、地质、地震等自然情况

1、地形、地貌

本项目场地地势较高,所在位置场区地基岩土体分4层:第一层素填土;第二层夹卵石淤泥质粉质黏土;第三层粉质黏土;第四层中等风化泥质粉砂岩;场区无不良地质现象,稳定性好,适宜建设加油站。

地震状况:根据国家地震局建设部的震发办(1992)160号文件及《中国地震烈度区划图(1990)》,该区地震烈度为6度。

2、气象水文条件

猇亭区属亚热带大陆季风气候区,一年四季分明,雨量充沛。根据区域周围气象台多年来的气象资料统计,主要气候特征如下:

年平均气温16.6℃;冬季平均气温5.0℃,极端最低温度-13.8℃;夏季平均气温26.7℃,极端最高温度40.8℃;年平均降水量1233mm,日最大降水量233.1mm,年平均相对湿度78%;年无霜期272天。

据近五年气象资料统计,该地区全年以静风为主,频率为42%;主导风向为ESE风,其次为SE风,风向频率分别为8%和7%;年平均风速1.61m/s。

1.2.2 建设项目投入生产或者使用后可能出现的最严重事故波及的范围,以及在此范围内的24小时生产、经营活动和居民生活的情况

本项目存在的主要危险、有害因素有:火灾、爆炸、电危害(包括雷电伤害、漏电伤害、静电伤害、触电等)、车辆伤害、健康危害、坍塌及其它事故所造成的危害和伤害等。其中可能对建设项目周边单位生产、经营活动或者居民生活造成影响的危险、有害因素为火灾爆炸。

本项目建设地点位于宜昌猇亭区猇亭大道,人口密度低,附近有

少量民居住宅,南侧为车检所,水平距离均在30米以上,且加油站三面均修建了约2.2米高的护坡,因此上述危害对区域内周边单位生产、经营活动或者居民生活的影响极为有限。该加油站按照国内现行的技术标准和规范进行安全设计,在重点危险部位设置有效安全设施,其危险、危害程度是完全可以接受的。

1.2.3 建设项目中危险化学品生产装置和储存数量构成重大危险源的储存设施与下列场所、区域的距离

建设项目中危险化学品生产装置和储存数量构成重大危险源的储存设施与下列场所、区域的距离见表。

序号 1 2 3 4 5 6 7 8 重要社会场所、区域 居民区、商业中心、公园等人口密集区域 学校、医院、影体育场(馆)等公共设施 供水水源、水厂及水源保护区 公路交通干线、地铁风亭及出入口 距离 500米范围内无该类设施 1000米范围内无该类设施 1000米范围内无该类设施 基本农田保护区、畜牧区、渔业水域和种子、种畜、厂区在开发区,无该类区域 水产苗种生产基地 河流、湖泊、风景名胜区和自然保护区 军事禁区、军事管理区 法律、行政法规规定予以保护的其他区域 无该类区域 2公里无该类区域 2公里无该类区域 本建设项目周边100米范围内没有重要公共建筑,只在站区南侧为车检所,附近有少量民居住宅,对本项目无直接的不良影响。 1.2.4 重大危险源概述

根据该加油站的安全评价报告的重大危险源辨识结果,本加油站建成后将构成贮存区重大危险源。

2 建设项目涉及的危险、有害因素和危险、有害程度 2.1 危险、有害因素

2.1.1 建设项目涉及具有爆炸性、可燃性的化学品危险类别及数据来

7

本项目涉及到的化学品有汽油、柴油、乙醇。

按《危险化学品名录》2002年版的界定,汽油属于第3.1类低闪点易燃液体,乙醇属于第3.2类中闪点易燃液体。

2.1.2 建设项目可能出现爆炸、火灾、中毒、灼烫事故的危险、有害因素

2.1.2.1 火灾、爆炸危险

1、危险化学品的火灾爆炸

本项目所涉及的危险化学品如汽油、柴油为易燃、易爆物质,若乙醇汽油、柴油部分管道和设备在一定条件下长期运行产生腐蚀、损坏,或操作错误,发生破裂、泄漏可能发生火灾爆炸。

乙醇汽油易挥发,蒸汽与空气混合形成爆炸性混合物,其爆炸范围比乙醇汽油更宽。乙醇汽油与氧化剂发生强烈反应,遇明火高热,有引起燃烧爆炸的危险。

2、工艺过程中的火灾爆炸 (1)卸油

油罐车卸油环节潜在的危险、有害因素及可能发生的故障和事故有:油品滴漏、油蒸气从卸油口逸出、产生静电火花、电气火花、雷电火花、明火等因素,皆可引发燃烧、爆炸事故。其产生的原因如下:

①油品滴漏。卸油时输油管线或鹤管破损,卸油泵的密封装置破损致使油品跑、冒、滴、漏。

②油蒸气从槽车卸油口逸出。油罐车卸油时将鹤管插入槽车油罐

8

时,油蒸气自然会从卸油口逸出。

③卸油时由于输油管、卸油油罐车、鹤管无防静电接地装置、接地装置损坏、接地电阻不符合要求、卸油泵和输油管线防静电接地装置损坏、防爆电气设备故障、现场人员使用手机或呼机、使用非防爆式照明灯具,均可导致产生静电火花或电气火花。

④遭遇明火。油罐车撞击、卸油现场人员吸烟或违章动火,导致明火产生。

⑤溢、漏或逸出的油品遇明火、静电火花、电气火花、雷电火花,可发生燃烧现象。若油蒸气经聚集后达到其爆炸极限,遇火源极易发生爆炸事故。

(2)加油

加油环节潜在的危险有害因素及可能发生的事故有:油蒸气外泄、油品外溢;产生静电火花或电气火花;遭遇雷电火花或明火,发生火灾。其产生的原因如下:

①油蒸气外泄。加油过程中,油枪与车辆加油孔之间留有空隙,加油时必然造成油蒸气外泄。

②油品外溢(冒油)。由于加油操作不当或计量仪表及防溢油联锁装置失灵等原因,可能导致加油时油品外溢。

③产生静电火花或电气火花。加油时由于防静电接地线接触不良、油品流速过快或喷溅、使用手机或呼机、穿、脱、拍打化纤服装形成静电;电器打火、使用非防爆照明灯具、防爆电气设备故障等原因,均有可能产生静电火花或电气火花。

9

(3)清罐

清罐环节潜在的危险有害因素或可能发生的事故有:罐内油气浓度较高而进入罐内作业可能发生窒息;罐体内残留油品使作业人员发生油品中毒;清罐时使用铁质器具、非防爆灯具而产生静电火花、电气火花、雷电火花或明火。其产生原因与前述的同类别相同。罐内残余的油蒸气遇静电、电气、雷电火花或明火后,均有可能发生燃烧爆炸事故。

(4)储存

储存环节潜在的危险有害因素或可能发生的事故有:油品渗漏;外渗或外漏的油蒸气聚集;产生静电火花、遭遇雷电或明火而发生燃烧、爆炸。其产生的原因如下:

①油品渗漏。油罐、输油管线、连接法兰及其相关设施由于制造缺陷或受到腐蚀,法兰密封联接不可靠和施工质量不符合要求等原因,可能导致油品渗漏。

②外渗或外漏的油蒸气聚集。由于油蒸气相对密度大,在通风不良的情况下,外泄、外漏的油蒸气易在管沟等低洼处聚集。

③发生燃烧、爆炸。外渗、外漏的油品经挥发、聚集并达到其爆炸极限后,若遇各类火源,极易发生燃烧、爆炸事故。

3、管理上的火灾爆炸危险性

管理缺陷而导致的燃爆危险性主要表现为管理制度不健全和无效管理,如:

(1)动火作业未办理管理手续,在禁区内违章动火,未作隔绝、

10

置换、分析、清除周围易燃物质等准备工作,消防和监护措施不力等。

(2)对各种火源管理不当,作业人员在禁区内吸烟或带火种进入;车辆加油不熄火,加油过程中从油箱溢出的汽油蒸气,遇车辆从排气管溅出的火花,也会引起火灾爆炸事故;在站区爆炸危险区域内使用手机、打火机也可引发火灾爆炸。

(3)在涉及危险化学品的场所内或罐区堆放易燃物质。 2.1.2.2 电危害 1、雷电伤害

若加油站未设置有效的避雷装置,避雷装置安装设计不合理,或检测维修不及时,在雷雨季节,站房、设备等均有遭受雷击的可能。雷雨天气进行加油、卸油等操作也易遭受雷电危害。

当油罐或装卸管线中的油品被雷击产生的雷电火花引燃可发生火灾、爆炸等严重事故。当建筑物被直击雷击中时,强大的冲击电压和雷电流会毁坏各种电气设备;强烈的机械振动会造成建筑物和设备、设施损坏;热效应会引起火灾或爆炸,雷电感应、球形雷和雷电侵入波都可能导致电气设备损坏,可导致大规模停电事故,并能造成生产环节的二次事故。雷击危害可导致火灾、爆炸、设备损坏、人员触电伤亡,甚至重大事故的发生。 2、静电伤害

汽油、柴油的电阻率一般在1010~1015Ω·cm左右,当沿管道与管壁摩擦和运输过程中受到振荡,都会产生静电,静电能量虽然不大,

11

但因其电压很高而易发生放电,出现的静电火花可能造成以下后果:

①引起火灾爆炸事故。

②产生电击现象。操作中形成的高电位静电极易对操作人员放电,产生电击现象,引起精神紧张或摔倒,容易造成工伤事故。 3、电气火灾

电气设备超负荷运转、电阻过大发热或绝缘不良、短路;电气线路安装不牢或接头松动打火;电线绝缘层老化、破损,导致并线短路,产生电火花起火;都可能导致火灾事故的发生。

4、触电

①本项目设有低压配电柜,用电设备较多,而本项目所在地夏天多雨、潮湿、高温,加速了电气设备、线路绝缘层的老化;如果在设计时考虑不周,所可能因采取安全技术措施不当,施工质量不符合要求,因漏电、触电,造成人员伤害的可能性很大。

②设备运行或检修、停送电的过程中,作业人员意外触电。 ③在防火区,使用不具防爆性能的电器(如灯、电机、开关、插座等),以及导线老化、短路产生电火花,亦可以引发火灾与爆炸。 2.1.3 建设项目可能出现的其它危险、有害因素分析 2.1.3.1车辆伤害

加油站内车辆往来频繁,如发生车辆碰撞、翻倒或由于司机驾驶错误造成汽车拖拽软管、损坏加油设施等,可能造成人员伤亡及财产损失,由于油料的泄漏,还可能引发火灾、爆炸、中毒和窒息等其它事故的发生。

12

2.1.3.2健康危害

乙醇汽油、柴油吸入、摄入或经皮肤吸收后对身体有害,可引起灼伤,对眼睛、皮肤粘膜和上呼吸道具有强烈刺激作用,吸入后,可引起喉、支气管的炎症、水肿、痉挛,化学性肺炎或肺水肿。特别是在清罐环节,罐内油气浓度较高而人员进入罐内作业可能发生窒息;罐体内残留油品使作业人员发生油品中毒。 2.1.3.3坍塌

加油站罩棚可能由于设计、材质、施工等原因存在缺陷,或因雪灾、风灾造成罩棚支座过载,导致罩棚坍塌。

除存在以上危险、有害因素外,人体的生理性和行为性因素可能造成的危险,如操作人员健康状况不良、错误指挥等也可能造成安全事故的发生。事故的发生往往是各种因素单独或相互作用的结果。

2.2 危险、有害程度

2.2.1 固有危险程度

2.2.1.1 项目工艺流程中涉及具有爆炸性、可燃性、腐蚀性的化学品数量、浓度、状态和所在的作业场所及其状况(见表2-2)。

表2-2项目工艺流程中涉及的化学品数量、浓度、状态和所在的作业场所及其状况

名称 危险类别 第3.1类低闪点极度易燃液体 3.2类易燃乙醇 中闪点液体 / 7.11 790 kg/m 3单位产品消生产场所储耗量(吨) 存量(吨) / 56.7 规格 所在的作业场所 3状况(温度、压力) 液体 汽油 700kg/m 加油岛,储罐区,站房 加油岛,储罐区,站房 液体 13

柴油 / / 50 830 kg/m 3加油岛,储罐区,站房 液体 2.2.1.2 项目涉及具有爆炸性、可燃性、腐蚀性的化学品固有危险程度

本加油站所经营的主要物品为车用乙醇汽油与柴油,对照《危险

化学品名录》,本项目生产过程中涉及的主要危险、有害物质为汽油

和乙醇。

说明:车用乙醇汽油是指在不添加含氧化合物的液体烃类中加入一定量变性燃料乙醇用于点燃式内燃机汽车的燃料。由于目前我国还没有编制车用乙醇汽油的安全技术说明书,故在本次评价中对车用乙醇汽油中的乙醇和汽油的基本特性分别进行分析。又因《车用乙醇汽油》标准中规定车用乙醇汽油只允许加入10%(上下幅度不超过0.5%)的变性燃料乙醇,其他技术要求与《车用无铅汽油》指标一致,所以在本项目评价中仍使用“汽油”这个概念。

1、汽油

汽油属第3.1类,为低闪点极度易燃液体,其蒸气与空气可形成爆炸性混合物,遇明火、高热极易燃烧爆炸。与氧化剂能发生强烈反应。其蒸气比空气重,能在较低处扩散到相当远的地方,遇火源着火回燃。

汽油的基本特性见附表1-2。 2、乙醇

属3.2类易燃中闪点液体,易燃,其蒸气与空气可形成爆炸性混合物,遇明火、高热能引起燃烧爆炸。与氧化剂接触发生化学反应或引起燃烧。在火场中,受热的容器有爆炸危险。其蒸气比空气重,能

14

在较低处扩散到相当远的地方,遇火源会着火回燃。

乙醇的基本特性见附表1-3。 3、车用乙醇汽油特点 (1)辛烷值高,抗爆性好。 (2)理论混合气热值与汽油相当。

(3)乙醇汽油含氧量高,存在自供氧效应,减少CO生存的条件,使CO较多转变成CO2,CO和H2排放量明显小于汽油,可有效地降低汽车尾气排放,改善能源结构,保护环境。

(4)乙醇汽油的着火极限比汽油宽。 4、柴油

危险特性:本品易燃,具刺激性。遇明火、高热或与氧化剂接触,有引起燃烧爆炸的危险。若遇高热,容器内压增大,有开裂和爆炸的危险。

柴油的基本特性见附表1-4。 2.2.2 风险程度

2.2.2.1工艺设备及设施危险性

本项目加油系统存在一定的危险性,本项目危险性最大的物质为汽油,火灾危险性为甲B类易燃液体,储存量较大(约90 m3),但操作及工艺过程危险性较低,根据分析评价可知,加油系统危险度等级为Ⅱ级,属中度危险。

2.2.2.2火灾、爆炸事故危险性

由安全评价和生产过程中危险有害因素辨识可知,火灾、爆炸是

15

该加油站存在的最危险,也是较容易发生的事故。 一般情况下,加油站发生火灾爆炸应满足以下条件:

①存在火源;

②泄漏油气达到可燃浓度; ③油气与空气混合物达到爆炸极限。

根据危险性分析加油站内油品泄漏与空气形成爆炸性混合物,并触及火源是加油站发生火灾爆炸事故的主要原因。

16

3 建设项目设立安全评价报告中的安全对策和建设采纳情况说明

1、宜昌市安特安全评价设备监理有限责任公司编制的《中国石油天然气股份有限公司湖北宜昌宜顺加油站设立安全评价报告》。

2、中国石油天然气股份有限公司湖北宜昌宜顺加油站已编制较完善的各项安全生产责任制和事故应急处理、安全生产操作规程,有完善的安全生产规章制度,并设置安全管理机构和配备专职安全管理人员。

3、本设计中,全部落实安全评价报告中的安全对策与建议,对总平面布置、建筑、工艺和设备、装置及消防、危险化学品贮存、装卸、运输等方面的安全设施和措施进行设计。

4 采用的安全设施和措施

17

4.1 项目选址、平面布置和建筑结构的安全措施

建设项目选址、平面布置和建筑结构中所采用(取)的安全措施及依据见表4-1。

表4-1 建设项目选址、平面布置和建筑结构中所采用(取)的安全措施及依据

项目 1 场地位置及地理条件 加油站的油罐、加油机和通气管管口与站外建、构筑物的防火距离拟按相关规定设计,见附表1-5 该加油站面临公路,其它三面均拟建高于2.2m的护坡 采取的安全措施 加油站的站址选择,符合城镇规划、环境保护和防火安全的要求,并应选在交通便利的地方。选址已办理规划手续,符合要求。 非城市建成区,属二级站 标准依据 《汽车加油加气站设计与施工规范》GB50156-2002 2006年版 第4.0.1条 《汽车加油加气站设计与施工规范》GB50156-2002 2006年版 第4.0.2条 《汽车加油加气站设计与施工规范》加油站不在城市城区内 GB50156-2002 2006年版 第4.0.3条 《汽车加油加气站设计与施工规范》GB50156-2002 2006年版 第4.0.4条 《汽车加油加气站设计与施工规范》GB50156-2002 2006年版 第5.0.1条 《汽车加油加气站设计与施工规范》GB50156-2002 2006年版 第5.0.2条 《汽车加油加气站设计与施工规范》GB50156-2002 2006年版 第5.0.3条 《汽车加油加气站设计与施工规范》GB50156-2002 2006年版 第5.0.4条 《汽车加油加气站设计与施工规范》加油岛按相关规定设计 GB50156-2002 2006年版 第5.0.5条 《汽车加油加气站设计与施工规范》GB50156-2002 2006年版 第5.0.8条 备注 车辆入口和出口分开设置 2 平面布置 站区内停车场和道路的车道宽度、转弯拟按要求设计,站内路面为水泥沙浆地面。 加油岛及汽车加油场地设罩棚,罩棚应采用非燃烧构料制作,其有效高度为6.5m 加油站内设施之间的防火距离,按相关规定设计 ,见附表1-6 3 建筑 加油站内的站房及其它附属建筑物的《汽车加油加气站设计与施工规范》耐火等级为二级。罩棚承重构件采用钢GB50156-2002 2006年版 筋全程焊接。 第11.2.1条 18

结构 加油站内,爆炸危险区域内的房间的地坪采用水泥沙浆地面。 加油站内无经营性的住宿、餐饮和娱乐等设施。 加油站内有绿化规划,已提出具体要求。 加油站的排水符合相关规定。 《汽车加油加气站设计与施工规范》GB50156-2002 2006年版 第11.2.4条 《汽车加油加气站设计与施工规范》GB50156-2002 2006年版 第11.2.10条 《汽车加油加气站设计与施工规范》GB50156-2002 2006年版 第11.3.1条 《汽车加油加气站设计与施工规范》GB50156-2002 2006年版 第9.0.12条

4.2 工艺和设备的安全措施

4.2.1 工艺的安全措施

工艺采取的安全措施及其依据见表4-2。

表4-3 建设项目工艺所采用(取)的安全措施及依据

采取的安全措施 依 据 钢制油罐的设计和建造,满足油罐在所承受外压作用下的强度要求,并应有良好的防腐蚀性能和导静电性能。钢制油罐所采用的钢板的厚度不小于5mm。 加油站的汽油罐和柴油罐(撬装式加油装置所配置的防火防爆油罐除外)埋地设置。 当油罐受地下水或雨水作用有上浮的可能时,采取防止油罐上浮的措施。 《汽车加油加气站设计与施工规范》 GB50156-2002 (2006年版) 第6.1.1条 《汽车加油加气站设计与施工规范》 GB50156-2002 (2006年版) 第6.1.2条 《汽车加油加气站设计与施工规范》 GB50156-2002 (2006年版) 第6.1.4条 《汽车加油加气站设计与施工规范》 GB50156-2002 (2006年版) 第6.1.9条 《汽车加油加气站设计与施工规范》 GB50156-2002 (2006年版) 第6.1.11条 备 注 油罐的进油管,向下伸至罐内距罐底0.2m处。 油罐的量油孔应设带锁的量油帽,量油帽下部的接合管宜向下伸至罐内距罐底0.2m处。 油罐通气管的设置,符合下列规定: 1、汽油罐与柴油罐的通气管,应分开设置。 2、管口应高出地面4m及以上。 《汽车加油加气站设计与施工规范》 3、沿建筑物的墙(柱)向上敷设的通气管管口,GB50156-2002 (2006年版) 应高出建筑物的顶面1.5m及以上。 第6.2.14条 4、当采用卸油油气回收系统时,通气管管口与围墙的距离可适当减少,但不得小于2m。

19

5、通气管的公称直径不应小于50mm。 6、通气管管口应安装阻火器。 7、当采用卸油油气回收系统和加油油气回收系统时,汽油通气管管口尚应安装机械呼吸阀。 4.2.2 设备的安全措施

设备安全措施是安全生产的重要环节,许多生产事故都是由于设备的不完善、故障、隐患等不安全因素所造成,因此必须对设备的安全性给予高度重视,要选择符合工艺要求、质量好的设备、管道、阀门,对可能的泄漏点进行经常性的检查、维护和控制,防患于未然。

设备采取的安全措施及其依据见表4-3。

表4-3 建设项目设备所采用(取)的安全措施及依据 采取的安全措施 依 据 油罐的各接合管,设在油罐的顶部,其中出油接合管设在人孔盖上。 当采用自吸式加油机时,每台加油机按加油品种单独设置进油管。 《汽车加油加气站设计与施工规范》 GB50156-2002 (2006年版) 第6.1.6条 《汽车加油加气站设计与施工规范》 GB50156-2002 (2006年版) 第6.2.6条 备 注 加油站的固定工艺管道宜采用无缝钢管。埋地钢管《汽车加油加气站设计与施工规范》 的连接应采用焊接。在对钢管有严重腐蚀作用的土GB50156-2002 (2006年版) 壤地段直埋管道时,可选用耐油、耐土壤腐蚀、导第6.2.8条 静电的复合管材。 相关设备器材的材质符合下列规定: a) 金属材料宜采用碳钢、不锈钢、铝等,不宜采用镀锌材料; b) 软管和密封垫材料宜采用耐乙醇的丁腈橡《新建与改建车用乙醇汽油加油站设胶、氯丁橡胶等;其它弹性体材料宜采用氟橡胶、计施工规范》(DB42/321-2005) 硅氟橡胶、聚硫橡胶和维通(偏氟乙烯与全氟丙乙第7.2条 烯的共聚体)等; c) 聚合物材料宜采用耐乙醇的缩醛树脂、尼龙、聚丙烯、聚四氟乙烯和玻璃纤维增强塑料等,不宜采用聚氨脂。 储存、输送车用乙醇汽油所用的储罐、泵、管道、《新建与改建车用乙醇汽油加油站设阀门、垫片、加油机等与车用乙醇汽油接触的设备器材的材质符合其对车用乙醇汽油的适用性。 计施工规范》(DB42/321-2005) 第7.1条 4.3电气的安全措施

本项目电气采取的安全措施及其依据见表4-4。

表4-4建设项目所采用(取)的电气安全措施及依据

20

采取的安全措施 加油站的供电电源采用电压为380/220V的外接电源。 埋地油罐与露出地面的工艺管道相互做电气连接并接地。 依 据 《汽车加油加气站设计与施工规范》 GB50156-2002 (2006年版) 第10.1.2条 《汽车加油加气站设计与施工规范》 GB50156-2002 (2006年版) 第10.2.4条 备 注 加油站的站房和罩棚等建筑物采用避雷带(网)保护。 即利用建筑物基础作接地体,将防雷保护接地,电气《汽车加油加气站设计与施工规范》 保护接地,弱电设施接地及等电位联接接地供用接地体,利用建筑物独立柱基础,地圈梁内敷设人工接地体,可靠焊接成电气通路,形成均压带。 380/220V供配电系统采用TN -S系统,供电系统的电缆金属外皮或电缆金属保护管两端均应接地,在供配电系统的电源端应安装与设备耐压水平相适应的过电压(电涌)保护器。 地上或管沟敷设的油品、液化石油气和天然气管道的始、末端和分支处设防静电和防感应雷的联合接地装置,接地电阻不大于30Ω。

GB50156-2002 (2006年版) 第10.2.5条 《汽车加油加气站设计与施工规范》 GB50156-2002 (2006年版) 第10.2.8条 《汽车加油加气站设计与施工规范》 GB50156-2002 (2006年版) 第10.3.1条 4.4 消防的安全措施

1、消防设施

该加油站消防器材依据《汽车加油加气站设计与施工规范》的各项规定及建设方提供的相关资料进行配置。未设消防给水,着火时主要用站内配置的消防器材灭火。站房内按《建筑灭火器配置设计规范》相关规定放置灭火器,本项目消防采取的安全措施及其依据见表4-5。

表4-5 建设项目所采用(取)的消防安全措施及依据

采取的安全措施 加油站的灭火器材配置: 1、每2台加油机设置1只4kg手提式干粉灭火器和1只6L泡沫灭火器;便利店、发电间门前集中设置8kg手提

依 据 《汽车加油加气站设计与施工规范》 GB50156-2002 (2006年版) 备 注 21

式干粉灭火器各2只。 2、地下储罐设35kg推车式干粉灭火器1个。 3、加油站配置灭火毯5块,沙子2m3。 4、其余建筑的灭火器材配置符合现行国家标准《建筑灭火器配置设计规范》GBJl40的规定。 第9.0.10条 车用乙醇汽油加油机、储罐的灭火器选用干粉灭火器。 《新建与改建车用乙醇汽油加油站设计施工规范》(DB42/321-2005) 第7.3条 加油站内爆炸危险区域以外的站房、罩棚等建筑物内的照明灯具,可选用非防爆型,但罩棚下的灯具选用防护等级不低于IP44级的节能型照明灯具。 《汽车加油加气站设计与施工规范》 GB50156-2002 (2006年版) 第10.1.9条

4.5 预防火灾与爆炸的对策措施

(1)应采取密闭方式卸油,卸油时应注意检查,防止油气大量泄漏; (2)加强对油罐液位计的检查,防止冒油;

(3)加强对加油设备、管道的维护保养,防止设备、管道及其附件破损、泄漏;

(4)在有火灾与爆炸危险的场所必须使用防爆型电气设备、设施; (5)站内应严禁烟火,特别要加强对进出站内车辆的管理。必须进行明火作业时,应按规定办理动火手续,采取可靠的防火防爆措施后,才可进行动火作业;

(6)禁止穿带钉鞋、化纤或其他易产生静电的衣帽进入危险区域; (7)油罐车进站静置10分钟后方可进行卸油作业,卸油作业时应严格控制流速;

(8)加油枪宜采用自封式加油枪,流量不应大于60L/min;

22

(9)站内建、构筑物及相关设备设施必须设置防雷防静电装置,并经常检查防雷防静电接地线,定期检测接地电阻,保证其完好; (10)禁止在危险场所使用铁制及其它易产生火花的工具; (11)禁止直接向塑料等绝缘容器加油;

(12)设固定或半固定消防设施和器材,一旦发生火灾事故,可以及时采取措施,扑灭火灾。

4.6 重大危险源的安全措施

在对重大危险源进行辨识和评价后,应对重大危险源制定出一套严格的安全管理制度,通过技术措施和组织措施,对重大危险源进行严格控制和管理。

通常情况下,重大危险源的管理应符合以下基本要求:

(1)加油站应制定一套严格的重大危险源管理制度。制度中应具体列出重大危险源的管理要求,同时要做好相关的记录工作。

(2)加油站对重大危险源应设置重大危险源的标志。标志中应简单列出相关的基本安全资料和防护措施。

(3)加油站应为重大危险源编制应急预案,并应进行必要的操练。 (4)按国家规定的时间对加油站的重大危险源进行安全评价。确保加油站的重大危险源保证在安全状态下运行。

5 事故预防及应急救援措施

5.1 应急救援组织或应急救援人员的设置或配备情况

中国石油天然气股份有限公司湖北宜昌宜顺加油站成立了事故救援组

23

织机构,下设应急救援领导小组、指挥部、应急救援办公室。以备在发生事故时制定有效的抢救方案和措施。企业按《生产经营单位安全生产事故应急预案编制导则》AQ9002-2006制订相关的安全事故应急预案,防患于未然。

5.2 消防队伍的依托或者建设情况

加油站指定了消防安全负责人。本站属城市消防支队管辖范围,10分钟可到达。

5.3 应急救援器材的配备情况

序 号 1 2 3 4 5 6 7 8 9 表5-1 应急救援器材的配备情况

品 种 单 位 数 量 自给正压式呼吸器 一般消防防护服 防静电工作服 胶鞋 氧气呼吸器 氧气包 医用胶布 医用沙布 医用棉签 套 套 套 双 个 个 卷 盒 袋 1 1 10 10 1 1 1 1 1 备 注 5.4 消防器材的配备情况

加油站每2台加油机设置4kg手提式干粉灭火器1只和6L泡沫灭火器1只,地下储罐设置35kg推车式干粉灭火器1个、便利店、发电间门前集中设置8kg手提式干粉灭火器各2只。站内设消防砂2立方米,消防砂存放于消防砂箱内。并配置灭火毯5块,设在砂箱旁。

5.5 应急救援措施

本项目生产过程中涉及的主要危险、有害物质为汽油和乙醇。 5.5.1 建立应急救援组织

1、确立组长。应急救援组织的组长应由单位行政一把手担任,全面负

24

责安全事故应急救援工作。行政副职担任副指挥长,负责管辖范围内的应急救援组织工作。

2、确立现场指挥。现场指挥一般应由现场值班最高领导担任。在指挥长、副指挥长到达事故现场前,现场指挥应统一指挥安全事故的应急救援工作,并将事故情况报告给指挥长、副指挥长。

3、确立各部门职责。各类安全事故应急救援方案编制部门即是本事故应急救援的主管部门,主管部门要做好有关部门的应急救援协调工作,同时要明确各职能部门在应急救援工作中的职责和作用。

4、建立救援队伍。现场值班人员是救援队伍的重要组成部分,要充分发挥前沿战斗堡垒的作用,同时应明确兼职应急救援队伍的组成及人员,做到招之即来,来之能战。

5、确定通信联络方式。将应急救援组织内部上至指挥长,下至最基层人员的联系电话,应急救援物资保管地点及人员的联系电话,以及单位所在地政府应急救援组织的电话、安全管理监督机构的电话、火警电话等进行汇总,发至组织内所有成员备用。 5.5.2 火灾的救援措施

发生火灾事故后,首先要正确判断着火部位和着火介质,立足于现场的便携式、移动式消防器材,立足于在火灾初期时及时扑救;如果是电气着火,则迅速切断电源,保证灭火的顺利进行;如果是大面积着火,要迅速切断着火单元的进料、切断与周围单元生产管线的联系,停机、停泵,迅速将物料倒至罐区或安全的储罐;发生火灾后,要在积极扑灭初起之火的同时迅速拔打火警电话向消防队报告,以得到专业消防队伍的支援,防止火势进一步扩

25

大和蔓延。

5.5.3 泄漏的救援措施

(1)汽油泄漏救援措施:迅速撤离泄漏污染区人员至安全区,并进行隔离,严格限制出入。切断火源。建立应急处理人员戴自给正压式呼吸器,穿防静电工作服。尽可能切断泄漏源。防止流入下水道、排水沟等限制性空间。少量泄漏:用砂土、蛭石或其它惰性材料吸收。或在保证安全情况下,就地焚烧。大量泄漏:构筑围堤或挖坑收容。用泡沫覆盖,降低蒸气灾害。用防爆泵转移至槽车或专用收集器内,回收或运至废物处理场所处置。 5.5.4 应急救援终止程序

事故处置结束后,现场领导小组安排抢救组人员以及岗位操作工对事故现场(重大部位需保护现场除外)进行洗消。确定安全后,由现场领导小组请示总指挥,由总指挥发布解除应急救援命令。同时通知相关部门,周边社区人员解除警报,恢复正常生产,生活秩序。 5.5.5 实施监督与日常检查

安全管理对策措施的动态表现就是日常监督与检查,主要对安全生产方面国家法律法规、技术标准规范和行政规章执行情况的监督与检查,对本单位制定的各类安全生产规章制度和责任制的落实情况的监督与检查。

1、应确定定期的安全活动制度,及时总结企业在执行安全中的情况。车间每月至少一次安全检查,管理人员和工人经常巡回检查,并定期对重点部位进行专业检查。

2、要加强对设备装置进行的监视、检查、定期维修保养,经常进行安全分析,对发生的事故或未遂事件、故障、异常工艺条件和操作失误等详作

26

记录和原因分析。

5.5.6 应急救援方案的培训、演练和完善

1、各类安全事故应急救援方案主管部门应将应急救援知识的培训、应急救援方案的演练列入年度工作计划,定期对有关人员进行培训,且每年至少进行一次演练。

演习的分类:演习可分为室内演习和现场演习两类,室内的演习又称组织指挥演习,它是检查指挥部门的领导和指挥、通讯、防化等各部门与救援部门之间的协调体系。现场演习即实地演习,根据其任务要求和规模可分为单项演习、多项演习、综合演习三种。

①单项演习,是针对性的完成应急救援任务中的某个单项科目而进行的基本操作,如个人防护演习、通讯演习、救护演习等的单一课目训练,它是局部演习,是全面综合演习不可分割的一个组成单元,也是局部演习、综合演习的基础。

②多项演习,是检验应急救援任务中的某个科目、某个部门准备情况,同应急单元之间的协调程度而进行的基本工作。

③综合演习,是检验指挥部的指挥、协调能力和救援专业队的救援能力及其配合情况,各种保障系统的完善情况及群众的避灾能力等。

2、演习内容

演习的基本内容包括各演习科目时间顺序要合乎逻辑性;各演习单位相互支援、配合及协调程度;加油站生产系统运行情况;站内应急情景:站内应急抢险;急救与医疗:站内洗消;防护指导,包括专业人员的个人防护及居民对毒气的防护;通信及报警讯号联络;事故区清点人数及人员控制;各

27

种标志的设立及由于危害区域的变化布设点的变更;交通控制;居民和无关人员的撤离以及有关撤离工作的演习内容;治安工作;政治宣传工作;事故的善后工作,包括防护区房屋内空气器具的消毒;向上级报告情况及向友邻单位通报情况;各专业队讲评要点;演习资料汇总需要的表格。

3、对应急救援方案的演练结果要进行评价。要针对演练中暴露出的问题和不足制定出整改措施,对原应急救援方案进行补充和完善。

28

6 安全管理机构的设置及人员配备 6.1 劳动安全管理机构设置及人员配备

要想保证加油站的安全,对周围环境不产生污染,对操作人员的身心健康有保障,必须保证加油站的各设备正常运行。

1. 加油站必须每班配备一名安全监督员,负责各项规章制度的执行情况

的监督。

2. 全站配备一名设备检查保养人员,负责站内各设备检修和保养。 3. 站长负责全站劳动卫生教育,定期对全站人员进行教育和督促。

7 安全设施投资概算

29

7.1 建设项目总投资概算

本建设项目建设投资概算值为300.90万元,其中建筑工程费用177.00万元,设备购置费116.60万元,其它费用7.30万元。

7.2 建设项目中安全设施投资概算和分类投资概算

本建设项目中安全设施投资共17万元,其中预防事故设施7万元,安全教育装备设施2万元,减少与消除事故影响设施5万元,其它安全投资3万元。详见表7-1。

序号 表7-1安全设施投资概算和分类投资概算表 单位:万元

占安全投资比品 种 总价 例 7.00 3.26 1.00 0.67 0.30 1.77 2.00 0.50 0.50 1.00 5.00 0.30 0.30 2.00 0.40 2.00 3.00 1.00 0.50 41.18% 11.76% 29.41% 17.65% 30

一 预防事故设施 1 2 3 4 5 视频监控 管道、设备等安全色防腐 消防设施、安全标志 场地、楼口等照明路灯 报警仪 二 安全教育装备和设施 1 2 3 安全培训材料 投影仪 电脑 三 减少与消除事故影响设施 1 2 3 4 5 设备安装橡胶垫等防噪声装置 应急照明灯 胶布防毒衣 劳保工作服 全身防火防毒服 四 其它安全投资 1 2

可行性研究报告、安全评价报批费用 道路、场地平整共用工程

3 4 5 保坎、围墙费用 外排沟 安全专篇编制及审查费 0.20 0.30 1.00 17.00 222.00 7.7% 100% 五 安全投资合计 六 工程项建设投资 七 安全投资占项目建设投资比例

7.3 安全设施投资概算占总投资概算的比例,安全设施分类投资概算占安全设施投资概算的比例

本建设项目建设投资概算值为300.90万元,其中安全设施投资共17万元,占建设投资概算5.6%。

本项目安全设施投资共17万元,其中预防事故施7万元,占安全设施投资41.18%;安全教育装备和设施2万元,占安全设施投资11.76%;减少与消除事故影响设施5万元,占安全设施投资29.41%;其它安全投资3万元,占安全设施投资17.65%。

8 结论和建议

8.1 结论

31

本设计通过对该建设项目的资料分析、类比工程论证,并对装置存在的固有危险因素和有害因素进行了风险辨识和分析。根据国、内外同类装置设计发展情况和国家现行有关安全生产法律、法规和部门规章及标准的规定和要求,现从下列几方面作出结论:

1、建设项目所在地的安全条件和与周围的安全防护距离

本项目拟建站址上架空电线应予建设施工前移装或绕开站区埋地敷设。2、建设项目选用的技术、工艺安全性

本项目拟采用国内外通行的汽车加油工艺,该工艺经过国内外众多加油站的运行,证明其控制简单、运行成熟、可靠性高。

3、建设项目选用的主要装置、设施安全性

本项目所选用的主要装置、设施型号符合项目要求,安全性符合要求。 4、建设项目采用(取)的安全设施水平

本项目系统装置存在一定的固有危险、有害因素,其系统危险程度中等;主要危险、有害因素有:火灾、爆炸、电危害(包括雷电伤害、漏电伤害、静电伤害、触电等)、车辆伤害、健康危害、坍塌及其它事故所造成的危害和伤害等。其可能发生的事故多为局部性的,如能按照国内现行的技术标准和规范进行安全设计,在重点危险部位设置有效的安全设施,其危险程度可控制在可接受范围内。

5、建设项目所达到的安全水平

在正常情况下,只要严格按照国家有关规范标准设计、施工,装置投产后加强安全管理,操作人员严格按操作规程操作,做好防护工作,各装置主要作业环境有害作业危害程度可以达到安全作业,从职业卫生的角度来看,

32

不发生突发性事故时,不会对人体产生明显的危害,作业环境是安全的。

8.2 建议

根据国、内外建设项目特别是同类装置(设施)建设项目的管理情况和趋势,从下列几方面提出建议:

1、主要装置、设施和安全设施及特种设备的订购

建设项目的主要装置、设施和安全设施应为正规企业生产,产品附有出厂合格证、产品说明书。属于特种设备的应附有安全技术规范要求的设计文件、产品质量合格证明、安装及使用维修说明、监督检验证明等文件。订购时宜采用招投标的形式,公开采购。

2、施工单位的选择

建设项目施工单位应选用信誉良好持有相应建设资质的施工单位。 3、主要原辅材料的选择

建设项目所选用的原辅材料应符合工艺技术要求。 4、投入试生产(使用)后的安全管理

建设项目投入试生产(使用)后,应根据实际情况及时完善相关安全管理制度,使安全管理落到实处。

5、其它方面

加油站每年应在财务计划、资金计划中,安排安全生产技术措施计划,在资金上予以保证,逐步改进和提高加油站安全生产的技术含量,从本质上实现安全生产。 附件清单:

1、建设项目地理位置图、工艺流程见图。

33

2、厂区总平面布置图、生产和储存装置(设施)、防雷防静电接地、消防设施及消防器材。

3、主要危险有害物质理化性质表。 4、加油站相关防火距离表。 5、加油站站内设施之间的防火距离。 6、建设项目所在地安全条件的分析情况。

本项目生产过程和装置及储存设施存在一定的固有危险,有害因素,如能按照国内现行的技术标准和规范进行安全设计,在重点危险部位设置有效安全设施其危险程度可控制在可接受范围内。本项目周边环境与自然条件对本建设项目基本无不良安全影响。

7、建设项目安全设施设计依据的国家现行有关安全生产法律、法规和部门规章及标准的目录。

附件一 图表

1、加油站工艺流程图

34

油库 → 油罐车 → 加油站 → 卸油 → 埋地油罐 → 油品管道 → 加油机 → 车辆

附图1-1: 加油工艺流程图

2、加油站主要装置名称、型号、材质、数量 附表1-1 :主要装置名称、型号、材质、数量

序号 1 2 设备名称 钢制储罐 税控加油机 规格型号 30立方米 材质 钢 钢 数量 5 4 备注 埋地

3、主要危险有害物质理化性质表

附表1-2:汽油

标 中文名:汽油 识 分子式:C5H12~C12H26

英文名:Gasoline; petrol 分子量:混合物 UN号: 1203 CAS号:8006-61-9 35

理 性 状:无色或淡黄色易挥发液体,具有特殊臭味 化 溶解性:不溶于水,易溶于苯、二硫化碳、醇、脂肪 性 熔点(℃):<-60 质 沸点(℃):40-200 燃 烧 爆 炸 危 险 性 毒 燃烧性:易燃 闪点(℃):-50 爆炸极限(V%):1.3-6.0 引燃温度(℃):415-530 相对密度(水=1):0.70-0.79 蒸汽密度(空气=1):3.5 燃烧产物:一氧化碳 二氧化碳 水 建规火险分级:甲 聚合危害:不聚合 稳定性:稳定 禁忌物:强氧化剂 危险特性:其蒸气与空气可形成爆炸性混合物,遇明火、高热极易燃烧爆炸。与氧化剂能发生强烈反应。其蒸气比空气重,能在较低处扩散到相当远的地方,遇火源着火回燃。 消防措施:喷水冷却容器,或将容器从火场移至空旷处。灭火剂:泡沫、干粉、二氧化碳。用水灭火无效。 急性毒性:LD50:67000mg/kg(小鼠经口)(120号溶剂汽油) LD50:103000mg/m3(小鼠吸入)(120号溶剂汽油) 性 刺激性:人经眼:家兔经眼:2mg/24h,重度刺激。 对 侵入途径:吸入、食入、经皮吸收 人 健康危害:吸入、摄入或经皮肤吸收后对身体有害。可引起灼伤。对眼睛、皮肤、 体 粘膜和上呼吸道具有强烈刺激作用。吸入后,可引起喉、支气管的炎症、水肿、痉挛,化危 学性肺炎或肺水肿。接触后可引起烧灼感、咳嗽、喘息、气短、头痛、恶心和呕吐等 险 皮肤接触:立即脱去污染的衣着,用肥皂水和清水彻底冲洗皮肤。就医。 急 眼睛接触:立即提起眼睑,用大量流动清水或生理盐水彻底冲洗至少15分钟。 吸 入:迅速脱离现场至空气新鲜处。保持呼吸道通畅。如呼吸困难,给输氧。如呼吸救 停止,立即进行人工呼吸。 食入:给饮牛奶 植物油洗胃和灌肠。就医。 工程控制:生产过程密闭,全面通风。 防 呼吸系统保护:一般不需要特殊防护,高浓度接触时可佩戴自吸过滤式防毒面具。 身体防护:穿防静电工作服。戴橡胶耐油手套。高浓度可戴化学安全防护眼镜。 护 其它防护:工作现场严禁吸烟。避免长期反复接触。 迅速撤离泄漏污染区人员至安全区,并进行隔离,严格限制出入。切断火源。建立应急泄 处理人员戴自给正压式呼吸器,穿防静电工作服。尽可能切断泄漏源。防止流入下水道、排漏 水沟等限制性空间。小量泄漏:用砂土、蛭石或其它惰性材料吸收。或在保证安全情况下,处 就地焚烧。大量泄漏:构筑围堤或挖坑收容。用泡沫覆盖,降低蒸气灾害。用防爆泵转移至理 槽车或专用收集器内,回收或运至废物处理场所处置。 危险性类别:第3.1类,低闪点易燃液体。 贮 储运注意事项:储存于阴凉、通风的仓间内。远离火种、热源,库温不宜超过30℃。防止 阳光直射,保持容器密封。应与氧化剂分开存放,切忌混储。采用防爆型照明。禁止使用 运 易产生火花的机械设备和工具。灌装流速应小于3m/s,储区应备有应急处理设备合适的收 容材料。 附表1-3:乙醇

标 中文名:乙醇;酒精 英文名:ethyl alcohol;ethanol CN号:32061 识 分子式:C2H12O 分子量:46.07 UN号:1170 理 性 状:无色液体,有酒香 化 溶解性:与水混溶,可混溶于醚、氯仿、甘油等多数有机溶剂。 性 稳定性:稳定 聚合危害:不聚合 禁忌物: 强氧化剂、酸类、酸酐、碱金属、胺

36

质 熔点(℃):-114.1 沸点(℃):78.3 相对密度(水=1):0.79 临界温度(℃):243.1 临界压力(MPa):6.38 蒸汽密度(空气=1):无资料 燃烧热(KJ/mol):1365.5 最小点火能(MJ): 无资料 饱和蒸汽压(KPa):5.33 (19℃) 燃 燃烧性:易燃 燃烧产物:一氧化碳、二氧化碳 引燃温度(℃):363 爆 闪点(℃):12 爆炸极限(V:V%):3.3-19 建规火险分级:无资料 危 易燃,其蒸气与空气可形成爆炸性混合物,遇明火、高热能引起燃烧爆炸。与氧化剂险 接触发生化学反应或引起燃烧。在火场中,受热的容器有爆炸危险。其蒸气比空气重,能性 在较低处扩散到相当远的地方,遇火源会着火回燃。 接触限值:最高容许浓度:中国MAC(mg/m3): 未制定标准 毒 急性毒性:LD50:7060 mg/kg(兔经口);7430 mg/kg(兔经皮) 性 LC50:37620 mg/m3,10小时(大鼠吸入) 健康危害:本品为中枢神经系统抑制剂。首先引起兴奋,随后抑制。 急性中毒:急性中毒多发生于口服。一般可分为兴奋、催眠、麻醉、窒息四阶段。患者进人 入第三或第四阶段,出现意识丧失、瞳孔扩大、呼吸不规律、休克、心力循环体 衰竭及呼吸停止。 危 慢性影响:在生产中长期接触高浓度本品可引起鼻、眼、粘膜刺激症状,以及头痛、头晕、疲乏、险 易激动、震颤、恶心等。长期酗洒可引起多发性神经病、慢性胃炎、脂肪肝、肝硬化、心肌损害及器质性精神病等。皮肤长期接触可引起干燥、脱屑、皲裂和皮炎。 消防措施:尽可能将容器从火场移至空旷处。喷水保持火场容器冷却,直至灭火结束。 灭火剂:抗溶性泡沫、干粉、二氧化碳、砂土。 皮肤接触:脱去污染的衣着,用流动清水冲洗。 眼睛接触:提起眼睑,用流动清水或生理盐水冲洗。就医。 吸 入:迅速脱离现场至空气新鲜处。就医。 食 入:饮足量温水,催吐。就医。 工程控制:生产过程密闭,全面通风。提供安全淋浴和洗眼设备。 呼吸系统防护:一般不需要特殊防护,高浓度接触时可佩戴过滤式防毒面具(半面罩)。 身体防护:穿防静电工作服、戴一般作业防护手套,眼睛一般不需特殊防护。 迅速撤离泄漏污染区人员至安全区,并进行隔离,严格限制出入。切断火源。建议应急处理人员戴自给正压式呼吸器,穿防静电工作服。尽可能切断泄漏源。防止流入下水道、排洪沟等限制性空间。小量泄漏:用砂土或其它不燃材料吸附或吸收。也可以用大量水冲洗,洗水稀释后放入废水系统。大量泄漏:构筑围堤或挖坑收容。用泡沫覆盖,降低蒸气灾害。用防爆泵转移至槽车或专用收集器内,回收或运至废物处理场所处置。 包装标志:易燃液体 包装类别:Ⅱ类包装 包装方法:小开口钢桶;小开口铝桶;安瓿瓶外普通木箱;螺纹口玻璃瓶、铁盖压口玻璃瓶、塑料瓶或金属桶(罐)外普通木箱。 消 防 与 救 护 泄 漏 处 理 包 装 贮 运 附表1-4:柴油

标 识 理 化 性 质

中文名:柴油 英文名: Diesel oil;Diesel fuel 危险性类别:第3.3类 高闪点易燃液体 CN号:无资料 UN号:无资料 性状:稍有粘性的棕色液体。 溶解性: 熔点: -18 相对密度(水=1):0.87-0.9 沸点:282-338 闪点:38 相对密度(空气=1): 无资料 饱和蒸汽压(KPa):无资料 爆炸下限: 无资料 爆炸上限: 无资料 临界温度:无资料 37

稳定性:稳定 毒 性 危险性概述 聚合危害:不聚合 禁配物:强氧化剂、卤素 建规火险分级: 燃烧性:易燃 燃烧产物:一氧化碳、二氧化碳 急性毒性: LD50:无资料 LC50:无资料 致癌性: 危险特性:本品易燃,具刺激性。遇明火、高热或与氧化剂接触,有引起燃烧爆炸的危险。若遇高热,容器内压增大,有开裂和爆炸的危险。 健康危害:皮肤接触可为主要吸收途径,可致急性肾脏损害。柴油可引起接触性皮炎、油性痤疮。吸入其雾滴或液体呛入可引起吸入性肺炎。能经胎盘进入胎儿血中。柴油废气可引起眼、鼻刺激症状,头晕及头痛。 其它危害:该物质对环境有危害,建议不要让其进入环境。对水体和大气可造成污染,破坏水生生物呼吸系统。对海藻应给予特别注意。 消防措施:消防人员须佩戴防毒面具、穿全身消防服,在上风向灭火。尽可能将容器从火场移至空旷处。喷水保持火场容器冷却,直至灭火结束。处在火场中的容器若已变色或从安全泄压装置中产生声音,必须马上撤离。灭火剂:雾状水、泡沫、干粉、二氧化碳、砂土。 泄漏处理:迅速撤离泄漏污染区人员至安全区,并进行隔离,严格限制出入。切断火源。建议应急处理人员戴自给正压式呼吸器,穿一般作业工作服。尽可能切断泄漏源。防止流入下水道、排洪沟等限制性空间。小量泄漏:用活性炭或其它惰性材料吸收。大量泄漏:构筑围堤或挖坑收容。用泵转移至槽车或专用收集器内,回收或运至废物处理场所处置。 急救措施:皮肤接触:立即脱去污染的衣着,用肥皂水和清水彻底冲洗皮肤。就医。眼睛接触:提起眼睑,用流动清水或生理盐水冲洗。就医。吸 入:迅速脱离现场至空气新鲜处。保持呼吸道通畅。如呼吸困难,给输氧。如呼吸停止,立即进行人工呼吸。就医。食 入:尽快彻底洗胃。就医。 防护措施:呼吸系统防护:空气中浓度超标时,建议佩戴自吸过滤式防毒面具(半面罩)。紧急事态抢救或撤离时,应该佩戴空气呼吸器。眼睛防护:戴化学安全防护眼镜。身体防护:穿一般作业防护服。手防护:戴橡胶耐油手套。其他防护:工作现场严禁吸烟。避免长期反复接触。 储存:储存于阴凉、通风的库房。远离火种、热源。应与氧化剂、卤素分开存放,切忌混储。采用防爆型照明、通风设施。禁止使用易产生火花的机械设备和工具。储区应备有泄漏应急处理设备和合适的收容材料。 消 防 与防 护 储存 运输 运输: 运输前应先检查包装容器是否完整、密封,运输过程中要确保容器不泄漏、不倒塌、不坠落、不损坏。运输时运输车辆应配备相应品种和数量的消防器材及泄漏应急处理设备。夏季最好早晚运输。运输时所用的槽(罐)车应有接地链,槽内可设孔隔板以减少震荡产生静电。严禁与氧化剂、卤素、食用化学品等混装混运。运输途中应防曝晒、雨淋,防高温。中途停留时应远离火种、热源、高温区。装运该物品的车辆排气管必须配备阻火装置,禁止使用易产生火花的机械设备和工具装卸。运输车船必须彻底清洗、消毒,否则不得装运其它物品。船运时,配装位置应远离卧室、厨房,并与机舱、电源、火源等部位隔离。公路运输时要按规定路线行驶。 4、加油站相关防火距离表

附表1-5:油罐、加油机和通气管管口与站外建、构筑物的防火距离(m)

级别 级 别 项 目

埋地油罐 一级站 二级站 50 三级站 50 通气管管口 50 加油机 50 38

重要公共建筑物 50

项 目 明火或散发火花地点 民用建筑物保护 类别 一类保护物 二类保护物 三类保护物 30 25 20 16 25 25 20 16 12 22 18 16 12 10 18 18 16 12 10 18 18 16 12 10 18 甲、乙类物品生产厂房、库房和甲、乙类液体储罐 其它类物品生产厂房、库房和丙类液体储罐以及容积不大于50m3的埋地甲、乙类液体储罐 室外变配电站 铁路 城市道路 快速路、主干路 次干路、支路 国家一、二级 架空 通信线 一般 18 25 22 10 8 不应跨越加油站,且不应小于1倍杆高 不应小于5m 不应跨越加油16 22 22 8 6 不应小于 1倍杆高 不应小于5m 不应跨越加油站,且不应15 18 22 8 6 不应 小于5m 不应 小于5m 15 18 22 8 6 15 18 22 6 5 不应小于5m 不应小于5m 不应跨越加不应跨越加油站,且不油站,且不应小于5m 架空电力线路 站,且不应小于1.5倍杆高 小于1倍杆高 应小于5m 注:1、明火或散发火花地点和甲、乙类物品及甲、乙类液体的定义应符合现行国家标准《建筑设计防火规范》的规定。 2、重要公共建筑物及其它民用建筑物保护类别划分应符合本规范附录C的规定。 3、对柴油罐及其通气管管口和柴油加油机,本表的距离可减少30%。 4、对汽油罐及其通气管管口,若设有卸油油气回收系统,本表的距离可减少20%;当同时设置卸油和加油油气回收系统时,本表的距离可减少30%,但均不得小于5m。 5、油罐、加油机与站外小于或等于1000KV·A箱式变压器、杆装变压器的防火距离,可按本表的室外变配电站防火距离减少20%。 6、油罐、加油机与郊区公路的防火距离按城市道路确定:高速公路、Ⅰ级和Ⅱ级公路按城市快速路、主干路确定,Ⅲ级和Ⅳ级公路按照城市次干路、支路确定。 7、与架空通信线和架空电力线路的距离不得按注3和注4折减。 注:本项目按二级站标准建设。

5、加油站站内设施之间的防火距离

附表1-6:加油站站内设施之间的防火距离(m)

设施名称

汽柴油罐 密闭加 站 消防泵房和消其他建筑变配道路 站区39

埋地油通气管卸油油 罐 汽埋地油柴罐 罐 口 油通气管密闭卸油点 加油机 站房 消防泵房和消防水池取水口 0.5 - 管口 - - 点 - 3 - 机 - - - - 房 防水池取水口 物、构筑物 电间 围墙 4 4 5 5 - 10 10 10 6 * - 5 7 7 8 6 6 5 5 6 6 - - - 3 - - - - 3 3 - - - - 1、加油站与非实体围墙的防火距离不应小于5m。 备注 2、站房、变配电间的起算点应为门窗。其他建、构筑物系指根据需要独立设置的汽车洗车房、润滑油储存及加注间、小商品便利店、厕所等。 3、表中:“-”表示无防火间距要求,“*”表示该设施不应合建。

建设项目安全设施设计依据的国家现行有关安全生产

法律、法规和部门规章及标准的目录

《危险化学品建设项目安全设施设计专篇编制导则(试行)》(安监总危化[2007]225号)

《中华人民共和国安全生产法》(中华人民共和国主席令第70号) 《中华人民共和国消防法》(中华人民共和国主席令第4号)

40

《危险化学品安全管理条例》(中华人民共和国国务院令第344号) 《爆炸危险场所安全规定》(劳部发[1995]56号)

《关于加强建设项目安全设施“三同时”工作的通知》(发改投资[2003]1346号)

《危险化学品建设项目安全许可实施办法》(国家安监总局令第8号) 《关于做好建设项目安全监管工作的通知》(安监管协调[2006]124号) 《湖北省工程项目劳动安全卫生评价、审查、验收暂行规定》(鄂经贸安[2000]848号)

《关于进一步加强建设项目(工程)劳动安全卫生预评价工作的通知》(安监管办字[2001]39号)

《关于开展重大危险源监督管理工作的指导意见》(安监管协调字[2004]56号)

《危险化学品建设项目安全评价细则》(安监总危化[2007]255号) 《建筑设计防火规范》(GB50016-2006)

《汽车加油加气站设计与施工规范》(GB50156-2002 2006年版) 《新建与改建车用乙醇汽油加油站设计施工规范》(DB42-321-2005) 《〈汽车加油加气站设计与施工规范〉车用乙醇汽油补充规定》(SHQ002-2001)

《钢质管道及储罐防腐蚀工程设计规范》(SYJ0007-1999) 《钢制卧式容器》(JB/T4731-2005) 《车用乙醇汽油》(GB18351-2004)

《建筑灭火器配置设计规范》(GB50140-2005)

41

《建筑物防雷设计规范》(GB50057-94 2000年版) 《火灾自动报警系统设计规范》(GB50116-1998) 《爆炸和火灾危险环境电力装置设计规范》(GB50058-92) 《重大危险源辨识》(GB18218-2000) 《安全标志》(GB2894-1996)

《常用化学危险品储存通则》(GB15603-1995) 《易燃易爆性商品储藏养护技术条件》(GB17914-1999) 《生产过程危险和有害因素分类与代码》(GB/T13861-1992)《企业职工伤亡事故分类》(GB6441-1986)

42

因篇幅问题不能全部显示,请点此查看更多更全内容