您好,欢迎来到意榕旅游网。
搜索
您的当前位置:首页PROJECT_STANDARDS_AND_SPECIFICATIONS_air_cooled_exchangers_Rev01

PROJECT_STANDARDS_AND_SPECIFICATIONS_air_cooled_exchangers_Rev01

来源:意榕旅游网
Page:1of19

KLMTechnology

Group

ProjectEngineering

Standard

Rev:01April2011

www.klmtechgroup.com

KLMTechnologyGroup#03-12BlockAronia,JalanSriPerkasa2TamanTampoiUtama81200JohorBahruMalaysia

PROCESSDESIGNOFAIRCOOLEDHEAT

EXCHANGERS(AIRCOOLERS)(PROJECTSTANDARDSANDSPECIFICATIONS)

TABLEOFCONTENT

SCOPE

REFERENCES

DEFINITIONSANDTERMINOLOGYSYMBOLSANDABBREVIATIONSUNITSGENERAL

HORIZONTALTYPEFANS

NumberofFans

FansinVariousDutiesTypes

RUSTPREVENTION

CHEMICALCLEANINGCONNECTIONS

OPERATINGTEMPERATUREANDPRESSUREAIR-SIDEDESIGN

GeneralRequirementsDESIGNCONSIDERATIONS

TUBE-SIDEFLUIDTEMPERATURECONTROLCOLDCLIMATECONSIDERATION

HighViscosity-HighPour-PointServicesWinterizationAPPENDIXAAPPENDIXBAPPENDIXC

2223334445566777810111112161719

Page2of19

KLMTechnology

Group

ProjectEngineeringStandard

PROCESSDESIGNOFAIRCOOLEDHEATEXCHANGERS

(AIRCOOLERS)(PROJECTSTANDARDSAND

SPECIFICATIONS)

Rev:01

April2011

SCOPE

ThisProjectStandardsandSpecificationscoverstheminimumprocessdesignrequirements,fieldofapplication,selectionoftypesanddesignconsiderationforaircoolers.REFERENCES

ThroughoutthisStandarddatedandundatedstandards/codesarereferredto.Thesereferenceddocumentsshall,totheextentspecifiedherein,formapartofthisstandard.Fordatedreferences,theeditioncitedapplies.TheapplicabilityofchangesindatedreferencesthatoccuraftertheciteddateshallbemutuallyagreeduponbytheCompanyandtheVendor.Forundatedreferences,thelatesteditionofthereferenceddocuments(includinganysupplementsandamendments)applies.

DEFINITIONSANDTERMINOLOGY

Bank-Oneormoresectionsincludingoneormoreunitsarrangedinacontinuousstructure.

BareTubeSurface-Outsidesurfaceofprimetubesbasedonlengthmeasuredbetweenoutsidefaceofheadertubesheetsinsquaremeters.

Bay-OneormoreK-Finsections,mountedonaselfsupportedstructurecompletewithmechanicalequipment.

FinnedTubeSurface-Totaloutsidesurface(exposedtoair)basedonlengthoftubesmeasuredbetweenoutsidefaceofheadertubesheetsinsquaremeters.ForcedDraftType-Designedwithtubebundleslocatedonthedischargesideofthefan.

InducedDraftType-Designedwithtubebundleslocatedonthesuctionsideofthefan.

Section-Assemblyoftwoheaders,finnedtubesandsidechannels.TubeBundle-Assemblyofheaders,tubesandframes.

Page3of19

KLMTechnology

Group

ProjectEngineeringStandard

PROCESSDESIGNOFAIRCOOLEDHEATEXCHANGERS

(AIRCOOLERS)(PROJECTSTANDARDSAND

SPECIFICATIONS)

Rev:01

April2011

Unit-Theair-cooledheatexchangeequipmentcoveredbyoneequipmentnumber,comprisingoneormoresections,thebundlestoperformonespecificduty.

SYMBOLSANDABBREVIATIONSSYMBOL/ABBREVIATIONA/VDNMAPNPSPUo

DESCRIPTIONAutovariable

DiameterNominal,mmManualAdjustablePitchNominalPipeSize,inch

Air-sidestaticpressuredrop,mbar(0.1kPa)

OverallHeatTransferCoefficient,W/m2.K(W/m2.°C)

UNITS

ThisStandardisbasedonInternationalSystemofUnits(SI)exceptwhereotherwisespecified.GENERAL

1.Aircooledexchangersareusuallycomposedofrectangularbundles

containingseveralrowsoftubesonatriangularpitch.Heattransferisgenerallycountercurrent,thehotfluidenteringthetopofthebundleandairflowingverticallyupwardthroughthebundle.

Aircooledunitshavebeensuccessfullyandeconomicallyusedinliquidcoolingforcompressorengineandjacketwaterandotherrecirculatingsystems,petroleumfractions,oils,etc.andalsoincondensingserviceforsteam,highboilingorganicvapors,petroleumstillvapors,gasoline,ammonia,etc.

2.Sinceairisauniversalcoolant,therearenumerousapplicationswhere

economicandoperatingadvantagesarefavorabletoair-cooledheattransferequipment.However,applicationsarelimitedtocaseswheretheambientairdrybulbtemperatureisbelowthedesiredcoolingorcondensingtemperature.

Page4of19

KLMTechnology

Group

ProjectEngineeringStandard

PROCESSDESIGNOFAIRCOOLEDHEATEXCHANGERS

(AIRCOOLERS)(PROJECTSTANDARDSAND

SPECIFICATIONS)

Rev:01

April2011

3.Whereexpensiveorinsufficientwatersuppliesareencounteredorwhere

coolingwaterpumpingortreatingcostsareexcessive,itisoftenfoundthatair-cooledunitsaredesirableforseveralservices.Theadverseconditionsofhighrelativehumidityorexcessivespacerequirementsoccasionallycreatehighcostsorinstallationdifficultiesforcoolingtowers.Insomeofthosecases,air-cooledheattransferequipmentoffersasatisfactorysolution.4.Fullconsiderationshouldbegiventoadequatewinterprotectionofair-cooled

unitsinstalledincoldclimates.Itisessentialthatallpossibilitiesoffreeze-upbeeliminatedandexternalrecirculationofhotairisnecessaryforseverewinterconditionswhentheunitissubjecttofreezingandheatingcoilsprovidedforprotectionagainstfreeze-upshallbeinaseparatebundleandnotpartoftheprocesstubebundle.5.Ifthefluidbeinghandledissubjecttowidevariationsinviscosityoverthe

rangeofatmospherictemperaturesencountered,provisionsmustbemadetocontroltheextentofcoolingatthelowerambientairtemperatures.6.Bundlesmaybefabricatedinwidthsto3.65m(12ft)anddepthsto8rows.

Usuallythemaximumdimensionsaredictatedbyshippingrequirements.Althoughstandardbundlesareavailableinlengthsof2.44m(8ft),3.05m(10ft),4.57m(15ft),6.07m(20ft),7.31m(24ft),10.36m(34ft),and12.2m(40ft).Bundlesmaybestacked,placedinparallel,orinseries,foragivenservice.Also,severalsmallservicesmaybecombinedinonebay.

Ingeneral,thelongerthetubesandthegreaterthenumberoftuberows,thelessexpensivethesurfaceonasquaremeterbasis.

7.Inmoderateclimatesaircoolingwillusuallybethebestchoiceforminimum

processtemperaturesabove65°C,andwatercoolingforminimumprocesstemperaturesbelow50°C.Betweenthesetemperaturesadetailedeconomicanalysiswouldbenecessarytodecidethebestcoolant.HORIZONTALTYPE

Unlessotherwisespecified,thehorizontaltypeispreferred.FANS

NumberofFans

Page5of19

KLMTechnology

Group

ProjectEngineeringStandard

PROCESSDESIGNOFAIRCOOLEDHEATEXCHANGERS

(AIRCOOLERS)(PROJECTSTANDARDSAND

SPECIFICATIONS)

Rev:01

April2011

Atleasttwofansshallbeprovidedforeachbay.AnydeviationfromthisrequirementwillneedthepriorapprovaloftheCompany.FansinVariousDuties

Where,forreasonsofcontrol,anair-cooledheatexchangerhastobeprovidedwithautomaticvariable-pitchfans,asinthecaseofoverheadcondensers,itshallnotshareitsfanswithair-cooledheatexchangersonotherduties,forexampleproductrun-downcoolers.Types

1.Twogeneralclassificationsofair-coolerfansare:

a.forceddrafttypewhereairispushedacrossthetubebundle;

b.induceddrafttypewhereairispulledthroughthebundle(seeFig.1).2.Forceddraftshouldbeselectedforallnormalapplications.Amongstother

reasons,theaccessibilityoffans,actuatorsanddrivesismuchbetterformaintenanceandthereisthusastrongpreferenceforthisarrangement.

Forceddraftshallbeselectedforcriticalandcondensingdutieswherethedifferencebetweenthedesignproductoutlettemperatureandthedesignairinlettemperatureis15°Corhigher.

Forceddraftshallbeselectedforallcoolingdutieswhereairoutlettemperatureswouldbehigherthanthosespecifiedaslimitingfortheinduced-draftarrangement.

3.Forcriticalcoolingorcondensingdutieswheretheproductoutlettemperature

fallsbelowapoint15°Cabovethedesignairinlettemperature(*),induceddraftmaybeconsideredprovidingtheairoutlettemperaturewillnotrisetoalevelhigherthanisacceptableforthefan,fanhubandbearingsforthegreasingsystemandforallstructuralcomponentsexposedtothehotairstream.ThedegreeofacceptabilityissubjecttotheCompany’sapproval.

Undernormaloperatingconditions,airoutlettemperaturesshouldnotexceed:--60°Cwithfansinoperation.

80°Cwithfreeconvectionontheairside.

Ahigheroutlettemperaturemaybeconsideredprovidingitdoesnotexceedtheoperatingtemperaturelimitsforthefanblades,thehub,thefanblade

Page6of19

KLMTechnology

Group

ProjectEngineeringStandard

PROCESSDESIGNOFAIRCOOLEDHEATEXCHANGERS

(AIRCOOLERS)(PROJECTSTANDARDSAND

SPECIFICATIONS)

Rev:01

April2011

adjustingmechanismandthebearingswhentheheatexchangerisatmaximumoperatingtemperaturewithfreeconvectionontheairside.Thetemperatureeffectofradiationundertheseconditionsshallalsobetakenintoaccount.Forthepowerfailurecase,takeamaximumairoutlettemperatureof15°Cbelowthemaximumproductinlettemperature.

*UnlessotherwiseagreedbytheCompany,theproductoutlettemperatureshallnotbelessthan10°Cabovethedesignairtemperature.

4.TheadvantagesofforcedandinduceddrafttypesarelistedinAppendixD.

Theseshouldbeweighedcarefullybeforedecidingonthechoiceofunit.5.Recommendations

a.Induced-draftunitsshouldbeusedwheneverhot-airrecirculationisapotentiallycriticalproblem.

b.Forced-draftunitsshouldbeusedwheneverthedesignrequirespour-pointprotection,orwinterization.However,considerationofpossiblesummerrecirculationmustbeaccountedforinsizingthefanstominimizethiseffect.RUSTPREVENTION

Thestructuralpartscanbegalvanizedorpickledandpaintedtopreventrustingofthesteel.

CHEMICALCLEANINGCONNECTIONS

Ifchemicalcleaningmaintenanceisspecified,connectionsshallbeprovidedperthefollowing:

a.ConnectionsshallbeinstalledonlyinnozzlesDN100mm(NPS4inch)andlarger.Forsmallernozzles,connectionswillbemadeintheattachedpipingbythepurchaser.

b.TheminimumsizeconnectionshallbeDN50mm(NPS2inch).

c.Connectionsshallbeinstalledhorizontally.Orientationwillbespecified.

d.Forbundlesinseriesorseries-parallelarrangement,onlyonechemicalcleaningconnectionneedbeprovidedintheinletnozzleandoneintheoutletnozzleofeachseriesgroup.

Page7of19

KLMTechnology

Group

ProjectEngineeringStandard

PROCESSDESIGNOFAIRCOOLEDHEATEXCHANGERS

(AIRCOOLERS)(PROJECTSTANDARDSAND

SPECIFICATIONS)

Rev:01

April2011

OPERATINGTEMPERATUREANDPRESSURE

ThemaximumanticipatedprocessoperatingtemperaturewillbeindicatedontheProcessDataSheet.AirCoolersshallbedesignedforatemperatureatleast28°Cabovethemaximumanticipatedtemperature.

Themaximumanticipatedoperatingpressure,whichshallincludeanallowanceforvariationsinthenormaloperatingpressurewhichcanbeexpectedtooccur,willbeindicatedontheAirCoolerSpecificationSheet.

Exceptforaircoolersoperatingunderavacuum,theinternaldesignpressureshallbe10%greaterthanthespecifiedmaximumoperatingpressure,butinnocaseshallthedifferencebelessthan2bar(200kPa).Theheadersonaircoolersoperatingunderavacuumshallbedesignedforaminimumexternalpressureof1bar(100kPa)unlessotherwisespecified.DesignpressuresshallbeindicatedontheProcessDataSheet.AIR-SIDEDESIGNGeneralRequirements

1.Suchenvironmentalfactorsasweather,terrain,mounting,andthepresence

ofadjacentbuildingsandequipmentinfluencetheair-sideperformanceofanair-cooledheatexchanger.

ThepurchasershallsupplytheVendorwithallenvironmentalfactorspertinenttothedesignoftheexchangeraspertheTable1.Thesefactorsshallbetakenintoaccountintheair-sidedesign.

2.AirCoolersshallbedesignedforsummerandwinterconditions.Thesummer

andwinterdesignairtemperaturesandhumiditiesshallbespecifiedinthejobspecifications.3.Forwinterdesignconditionstheminimumtubewalltemperatureshallbeat

least22°Chigherthanpourpointtemperatureforbothnormalandminimumdesignthroughput.4.Properfoulingresistanceshallbeappliedtotheinsidesurfaceofthetube.

Page8of19

KLMTechnology

Group

ProjectEngineeringStandard

PROCESSDESIGNOFAIRCOOLEDHEATEXCHANGERS

(AIRCOOLERS)(PROJECTSTANDARDSAND

SPECIFICATIONS)

Rev:01

April2011

5.Allheattransfersurfacesandcoefficientsshallbebasedontotaleffective

outsidetubeandfinsurface.6.Whencalculatingheattransfercoefficients,theinsidefoulingandinsidefluid

filmresistanceshallbemultipliedbytheratioofthetotaleffectiveoutsidesurfacetothetotaleffectiveinsidesurface.7.Theeffectivetubewallandfinmetalresistanceshallbeincludedin

calculatingheattransfercoefficients.8.Pressuredropsshallnotexceedthemaximumallowedvaluesspecified.

Theseindicatethetotalpressuredropsacrossnozzles,headersandtubes.9.Foulingfactoronairsideofexchangersshallbe0.35m2.K/kW(0.002

h.ft2.°F/Btu).10.Theneedforairflowcontrolshallbeasdefinedbythepurchaseronthebasis

ofspecificprocessoperationrequirements,includingtheeffectofweather.Variousmethodsofcontrollingairflowareavailable.

Thetypeultimatelyselectedisdependentonthedegreeofcontrolrequired,thetypeofdriverandtransmission,equipmentarrangement,andeconomics.Asaguide,thevariousmethodsinclude,butarenotlimitedto,simpleon-offcontrol,on-offstepcontrol(inthecaseofmultiple-driverunits),two-speedmotorcontrol,variable-speeddrivers,controllablefanpitch,manualorautomaticlouvers,andairrecycling.

11.Fanselectionatdesignconditionsshallbesuchthatatconstantspeedthe

faniscapableofproviding,byanincreaseinbladeangle,a10percentincreaseinairflowwithacorrespondingpressureincrease.12.Intheinquirythemaximumandminimumdesignambienttemperaturesunder

whichfansanddriverswilloperate,aswellasanyspecificrequirementsrelatingtothesizingofdriversandtransmissionsshallbestated.13.Formechanicalcomponentslocatedabovethetubebundledesign

temperatureshallbeequaltomaximumprocessinlettemperatureunlessotherwisespecified.DESIGNCONSIDERATIONS

1.Designmaximumambientairtemperatureshouldbeselectedsothatitwill

notbeexceededmorethan1-2percentofthetotalannualhourlyreadingsbasedonatleast5consecutiveyears.Lowerfiguresmeanasmaller

Page9of19

KLMTechnology

Group

ProjectEngineeringStandard

PROCESSDESIGNOFAIRCOOLEDHEATEXCHANGERS

(AIRCOOLERS)(PROJECTSTANDARDSAND

SPECIFICATIONS)

Rev:01

April2011

exchangerbuttheyalsoindicateaquestiononperformanceduringhottestweather.Dailytemperaturechartsaswellascurvesshowingnumberofhoursandtimeofyearanygiventemperatureisexceededvaluableandoftennecessaryinestablishinganeconomicaldesigntemperature.SeeTableA.1inAppendixAasatypicalstudy.

thetheareair

2.Unitsshouldpreferablybeplacedintheopenandatleast23-30mfromany

largebuildingorobstructiontonormalwindflow.Ifcloser,therecirculationfromdowndraftsmayrequireraisingtheeffectiveinletairtemperature1-2°Cormoreabovetheambientselectedforunobstructedlocations.

Ifwindvelocitiesarehigharoundcongestedareas,theallowanceforrecirculationshouldberaisedabove2°C.

3.Unitsshouldnotbelocatednearheatsources.Experiencecautionsthatunits

nearexhaustgasesfromenginescanraiseinletair8°Cormoreabovetheexpectedambient.4.HotAirRecirculation

Problemsassociatedwithhotairrecirculationarethedirecteffectofpoorexchangerdesignandlocation.Minimumallowabledistancesbetweenaircoolersandotherprocessequipmentshouldbeconsidered.These,however,arebasedonsafetyrequirementsandshouldbeaccordinglyincreasedifrecirculationposesapotentialproblem.Otherrecommendationsforcombatinghotairrecirculationinclude:---Usinginduceddraftfanswhichforcetheairawayfromthebundle.

Bafflesand/orastackontopofthebundleforaforceddraftunit(orfanonaninduceddraftunit)willalsodirecttheairawayfromthebundle.

Humidificationsectionsorairwashers:Ifthegeographiclocationissuchthattherelativehumidityislowmostoftheyear,ahumidificationsectioncouldbeinstalledbelowtheunit.This,ineffect,moisturizestheinletairdowntoitswetbulbtemperaturewhichcouldbe5°Cto11°Ccoolerthanambient.However,careshouldbetakentoinsurethatairenteringthetubebundleisdry.

A-Frame,V-Frameandverticalbundlearrangementsshouldnotbeusedifrecirculationisapotentialproblem.

Watersprayingisnotrecommendedforalleviatingexistinghotairrecirculationproblemsexceptasatemporarysolution.Ifthebundleissprayeddirectly,tube-to-finbonding,fouling,andcorrosionproblems

--