一 概述 ······························································································································· 1 二 技术参数 ······················································································································· 1 2.1额定参数 ······················································································································ 1 2.2 主要技术性能 ·············································································································· 1 2.3 绝缘性能······················································································································ 2 2.4 抗电磁干扰性能 ·········································································································· 3 2.5 机械性能······················································································································ 3 三 装置功能 ······················································································································· 4 四 装置硬件 ······················································································································· 4 4.1 保护CPU 模块 ············································································································· 4 4.2 人机对话模块 ·············································································································· 5 4.3 开入开出模块 ·············································································································· 5 4.4 电源模块······················································································································ 5 五. 保护原理及整定说明 ·································································································· 5 5.1 短路保护······················································································································ 5 5.2 过载反时限保护 ·········································································································· 6 5.3 三相不平衡保护 ·········································································································· 7 5.4 低电压保护 ·················································································································· 7 5.5 过电压保护 ·················································································································· 8 5.6 漏电闭锁保护 ·············································································································· 8 5.7 选择性漏电保护(分开关) ······················································································· 8 5.8 漏电保护(总开关) ···································································································· 10 5.9 瓦斯保护···················································································································· 10 5.10 风电闭锁保护 ·········································································································· 11 六 试验功能 ····················································································································· 11 七 用户接线说明 ·············································································································· 12 八 人机接口系统的使用方法 ··························································································· 13 8.1 实时循环显示菜单说明 ····························································································· 13 8.2 主菜单操作说明 ········································································································ 15 8.3子菜单操作说明 ········································································································· 15 九.各部件安装尺寸 ········································································································ 21 十.保护装置清单表 ········································································································ 24 十一.典型接线原理图 ···································································································· 25

GCS2322数字式低压保护测控装置

一 概述

GCS2322数字式低压保护测控装置是在多年实践应用和运行经验的基础上,采用32位高速DSP数字处理技术,为各系列矿用隔爆型低压配电柜研制推出的新一代专门设计的集保护、测控、通信一体化装置,广泛适用于电力、煤矿、水利、石油、化工等行业3300V及以下电压等级的含有爆炸性气体(甲烷)和煤尘、粉尘等特殊环境,是实现煤矿井下电力自动化控制的终端设备,具有CAN及RS485双通信接口,以实现供电系统的各种保护功能及自动化控制功能。开放的通信平台,方便与各种通信分站连网,可以真正的实现煤矿井下电力自动化控制要求。

装置能与380V、660V、1140V、3300V额定电压等级,额定电流可至1000A 的各种型号的馈电开关配套使用,可替代传统各型模拟保护器和微电脑保护器,也可用于老开关的更新、改造。

二 技术参数

2.1额定参数 2.1.1 工作电源

额定电压:交流100V、50Hz,来自电压变压器的输出电压供电。 该装置在交流电压70V~150V范围内变化时能正常工作。 2.1.2 额定交流数据

a) 交流电压 :380V、660V、1140V、3300V b) 交流电流:<1000A c) 额定频率:50Hz 2.1.3 功率消耗

a) 直流回路:正常工作时不大于20W,装置动作时不大于25W。 b) 交流电压回路:每相不大于0.5VA c) 交流电流回路:每相不大于1.0VA; 2.2 主要技术性能

2.2.1 采样回路精确工作范围及误差见表1

表1 采样回路精确工作范围及误差

电量 保护回路 测量范围 额定误差 1

GCS2322数字式低压保护测控装置

三相电压 三相电流 零序电压 零序电流 0V-1500V 5A-8000A 0V-50V 0mA-100mA ±5% ±5% ±5% ±5mA

测量回路的基准值为额定值时的误差为额定误差。 2.2.2 过载能力

交流电流回路:2倍额定电流,连续工作; 10倍额定电流,允许10秒; 交流电压回路:1.2倍的额定电压,连续工作。 2.2.3 接点容量

出口触点容量:5A/250VAC 5A/30VDC 2.2.4 各类元件定值误差

电流元件定值误差:<±5% 电压元件定值误差:<±5% 时间元件:<±50ms

方向元件角度误差:<±5度

2.2.5 整组动作时间(包括继电器固有时间)

速动段的固有动作时间:1.2倍整定值时,误差不大于50ms 2.3 绝缘性能 2.3.1 绝缘电阻

装置的带电部分和非带电部分及外壳之间以及电气上无联系的各电路之间用开路电压500V 的兆欧表测量其绝缘电阻值,正常试验大气条件下各等级的各回路绝缘电阻不小于20M。 2.3.2 介质强度

在正常试验大气条件下,装置能承受频率为50Hz 、电压2000V 历时1 分钟的工频耐压试验而无击穿闪络及元件损坏现象。试验过程中任一被试回路施加电压时其余回路等电位互联接地。 2.3.3 冲击电压

在正常试验大气条件下,装置的电源输入回路、交流输入回路、输出触点回路对地以及回路之间能承受1.2/50µs 的标准雷电波的短时冲击。电压试验开路试验电压5kV。 2.3.4 耐湿热性能

装置应能承受GB/T 2423.9 规定的恒定湿热试验。试验温度40℃±2℃、相对湿度93%±3%、试验时间为48h,在试验结束前2小时内根据2.3.1 的要求测

2

GCS2322数字式低压保护测控装置

量各导电电路对外露非带电金属部分及外壳之间电气上不联系的各回路之间的绝缘电阻,绝缘电阻不小于1.5M。介质耐压强度不低于2.3.2 规定的介质强度试验电压幅值的75%。 2.4 抗电磁干扰性能 2.4.1 脉冲干扰

装置能承受GB/T 14598.13-1998规定的干扰试验。试验电压频率为100kHz 和1MHz,试验电压为共模2500V、差模1000V的衰减振荡波。试验时给被试装置预先施加电源。按GB/T14598.13 第3.1.1 的表所列临界条件叠加干扰试验电压装置不误动不拒动。 2.4.2 快速瞬变干扰

装置能承受GB/T 14598.10-1996 标准规定的IV 级4kV快速瞬变干扰试验。 2.4.3 静电放电

装置能承受GB/T 14598.14-1998 标准规定的IV 级空间放电15kV 、接触放电8kV 静电放电试验。 2.4.4 辐射电磁场干扰

装置应能承受GB/T 14598.9-1995 标准规定的严酷等级为III级的辐射电磁场干扰试验。 2.4.5 浪涌

通过GB/T 17626.5 1999 标准规定的浪涌冲击抗扰度III级干扰试验(共模2000V、差模1000V)。 2.5 机械性能 2.5.1 振动

装置能承受GB/T 7261-2000《继电器及装置基本试验方法》 中16.2.3 规定的严酷等级为1 级的振动响应试验;装置能承受GB/T 7261-2000 中16.2.3 规定的严酷等级为1 级的振动耐久试验。 2.5.2 冲击

装置能承受GB/T 7261-2000 中17.4.1.1 规定的严酷等级为1 级的冲击响应试验;装置能承受GB/T 7261-2000 中17.5.1 规定的严酷等级为1 级的冲击耐久试验。 2.5.3 碰撞

装置能承受GB/T 7261-2000 中18.4 规定的严酷等级为1级的冲击碰撞试验。

2.5.4 环境条件

a) 环境温度

3

GCS2322数字式低压保护测控装置

工作温度:-25℃-- +55℃ 贮存温度:-40℃ -- +85℃

b) 相对湿度:最湿月的月平均最大相对湿度为90% 同时该月的月平均最低温度为25℃且表面无凝露最高温度为+40℃时,平均最大相对湿度不超过50%

c) 大气压力:66kPa-110kPa 。

三 装置功能

保护功能 短路保护 过载保护 监控功能 遥测:三相电流、三相电压、系统电压、零序电压、零序其他功能 通信功能 与主站对时 三相不平衡保护 电流、有功、功率因数、漏远方修改保护定值 断相保护 电电阻、瓦斯浓度、温度等。 保护事件存储 漏电保护 遥信:开关位置、远控闭锁、开关量事件存储 漏电闭锁 瓦斯、风电闭锁等。 SOE事件存储 选择性漏电保护 遥脉:计算电度、电表电度电度量存储 低电压保护 等。 远方信号复归 过电压保护 遥控:本馈电开关遥控合闸现场模拟试验功能 瓦斯保护 和分闸。 风电闭锁

CAN:1路 RS485:1路 四 装置硬件

装置的硬件部分采用模块化设计,主要有保护CPU模块、人机对话模块、开入开出模块、电源模块四部分组成,各模块之间连接可靠,性能稳定,根据各厂家馈电开关的不同,人机对话模块可分开安装,也可一体安装,使用非常灵活,方便与不同的低压馈电开关配套。 4.1 保护CPU 模块

保护CPU模块采用32位DSP+CPLD核心高速数据处理器。可以实现每秒80兆次浮点运算,64K x 16位片内RAM存贮器;64K x 16位EPROM存贮器,存贮固化程序,1024 x8位存储定值安全可靠。

保护CPU 模块采用的数据采集部分由高可靠性的高精度的A/D转换器及硬件

4

GCS2322数字式低压保护测控装置

加软件数字滤波回路组成。A/D 转换芯片具有转换速度快、采样偏差小、超小功耗及稳定性好等特点。本装置的采样回路可通过软件调节采样精度具备高度的可靠性。

保护CPU 模块采用了多层印制板及表面封装工艺,外观小巧、结构紧凑、大大提高装置的可靠性及抗电磁干扰能力。 4.2 人机对话模块

显示模块是基于CPU开发的人机界面,它可以提供128X64的宽温液晶(液晶的背光节电设计),中文汉化显示,通俗易懂,支持6个LED位置显示灯分别显示当前运行状态。可与主机一体装配,也可独立分开装配,显示模件可用于设备的人机交互, 完成键盘处理、液晶显示等功能。插件上的显示窗口采用3行×16汉字的液晶显示器,人机界面清晰易懂,同时还配置了丰富的灯光指示信息使本装置的运行信息更为直观。RS485通信接口采用屏蔽双绞线。人机对话模块与保护CPU模块之间的通信连接件采用专用接插件,使装置运行更加可靠。 4.3 开入开出模块

开入部分包括电压、电流输入和开关量输入两个部分。开出部分包括分励脱扣的保护动作出口、用于失压脱扣的出口、用于遥控跳闸的跳闸控制出口、用于遥控合闸的合闸控制出口、用于模拟试验的试验出口以及信号出口等。 4.4 电源模块

装置供电由电压变压器供电,根据需要,电源模块可采用带有失压延时功能的高可靠性开关电源,具有失压延时功能。在电网失电时,开关电源的电压输出的延时时间大于3秒,保证保护装置在短时失电时能正常工作,并启动失压保护和记录电网失电的故障信息。本开关电源模块有效的解决了以往因交流供电而当电网失电保护即不能正常工作的缺点!

五. 保护原理及整定说明

5.1 短路保护 5.1.1 保护原理

对开关负载侧任一相出现的短路故障,本装置设置短路保护,当出现短路故障时瞬时跳闸。短路保护原理可选择鉴幅或相敏保护原理。 5.1.2定值单及整定说明

5

GCS2322数字式低压保护测控装置 1.短路保护的定值单如下: 定值 短路保护投退 保护原理 短路倍数定值 短路保护延时 2.整定说明

短路电流的整定值一般设为线路额定电流的5-8倍,时间整定为0秒。 鉴幅式:某相电流幅值超过短路电流(额定电流×短路倍数)时动作。 相敏式:当任意两相电流幅值超过短路电流且功率因数≥0.82 时动作, 如果有任何一相电流超过10 倍额定电流,那么直接跳短路故障,以检测 近端短路。 5.2 过载反时限保护 5.2.1 保护原理

定值范围 投/退 鉴幅/相敏 1-8倍 0.00s-99.99s 步长 / / 1倍 0.01S

过载动作时间采用反时限实时计算,具有热记忆特性,动作时间表如下:

过载保护在1.2倍额定电流时启动,反时限特性公式如下:

式中:k=负荷电流/额定电流,tp 为过载常数。Kx为过载系数。

过载保护利用热积累实现断续过载情况下的过载保护,当负荷电流小于额定 电流时,热积累能量开始散热。 5.2.2定值单及整定说明

6

GCS2322数字式低压保护测控装置

1.过载保护的定值单如下:

定值 过载保护 过载电流 定值范围 投/退 1-9999A 步长 / 1A 2.整定说明

过载保护具有能量累积释放功能,过载电流一般按照线路实际的额定电流整定,过载保护在1.2倍过载电流时启动,根据过载动作时间表进行动作,闭锁90S后自动复位。 5.3 三相不平衡保护 5.3.1 保护原理

三相不平衡保护元件是在其中一相电流大于30A以上时才投入判别,不平衡判别系数为最大相电流减最小相电流再除以最大相电流后所得。 5.3.2定值单及整定说明

1.三相不平衡保护的定值单如下:

定值 不平衡保护投退 不平衡系数 保护延时 5.4 低电压保护 5.4.1原理概述

定值范围 退/告警/跳闸 30%--100% 0s-240s 步长 / 1% 1S 装置包含一段低电压保护,当线电压小于低电压保护定值时,低电压保护经整定延时跳闸。低电压保护在合位时投入。 5.4.2定值单及整定说明 1.低电压保护的定值单如下: 定值 低电压保护投退 低电压定值 定值范围 退/告警/跳闸 50%-99% 步长 / 1% 7

GCS2322数字式低压保护测控装置

低电压保护时限 2.整定说明

低电压定值一般整定为额定电压的70%。 5.5 过电压保护 5.5.1原理概述

0s-240s 1s

装置包含一段过电压保护,当任一线电压或系统电压大于过电压保护定值时,过电压保护经整定延时跳闸。 5.5.2定值单及整定说明 1.过电压保护的定值单如下: 定值 过电压保护投退 过电压定值 过电压时限 2.整定说明

过电压定值一般整定为额定电压的120%。 5.6 漏电闭锁保护 5.6.1原理概述

开关合闸前对供电线路对地绝缘情况进行检测。当绝缘电阻低于下表的阻值时闭锁合闸。当主电路绝缘阻值上升到闭锁值1.5倍时,自动解除漏电闭锁。

电压等级 闭锁阻值

5.6.2定值单及整定说明

定值 漏电闭锁保护投退 漏电闭锁电阻定值 5.7 选择性漏电保护(分开关) 5.7.1原理概述

动作电阻值如下:(1140V等级,1K的漏电动作时间≤30mS)

8

定值范围 投/退 100%-130% 0s-240s 步长 / 1% 1s 380V 7 kΩ+20% 660V 22kΩ+20% 1140V 40 kΩ+20% 定值范围 投/退 0.0-200.0KΩ 步长 / 0.1KΩ GCS2322数字式低压保护测控装置

电压等级 动作阻值

380V 3~7kΩ 660V 5~13kΩ 1140V 5~13kΩ 5.7.2定值单及整定说明 1.漏电保护的定值单如下: 定值 选漏保护投退 零序电压启动值 零序电流启动值 零序功率方向投退 选漏动作时限 选漏保护跳闸投退 2.整定说明

U0、I0 的整定值建议如下:

电压等级 零序电压Uo 零序电流Io 380V 2V 10mA 660V 3V 15mA 1140V 4V 20mA 定值范围 退/告警/跳闸 0.1V—99.9V 0.000-100.0mA 投/退 0.00s-99.99s 告警/跳闸 步长 / 0.1V 0.1mA / 0.01S / “选漏保护”建议动作时间设置为30mS。

若遇到“选择性漏电保护”动作不正常,且检查外部选漏连接线路(如零序互感器、零序电压变压器及方向、漏电试验电阻等)都没有问题的情况下,可适当调节U0、I0的值来满足动作要求。 调节原则为:

1. 若选漏动作电阻值偏大,I0、U0门槛值均应提高;反之,可以稍降低;

而且,调整时应以调节I0门槛值为主;

2. 当用户使用环境潮湿、电缆长度偏长,即电网电容偏大的情况下,应降

低U0 门槛值,可以稍提高I0 门槛值;反之,应提高U0 门槛值,可以稍降低I0门槛值;

3. 若在大电机起动时,保护装置受干扰易误动,应稍提高U0 门槛值,而I0

基本不变;

4. 总之,提高U0、I0 门槛值,使本支路保护装置更难动作;降低U0、I0 门

9

GCS2322数字式低压保护测控装置

槛值,使本支路保护装置更易动作。

依据上述原则,合理调节U0、I0 门槛值已经能够有效防止电机启动时选漏误动作情况。

5.8 漏电保护(总开关) 5.8.1原理概述

动作电阻值如下:(1140V等级1K电阻接地时,漏电动作时间≤50mS)检测原理为附加直流法。

电压等级 动作阻值

5.8.2定值单及整定说明

定值 漏电保护投退 漏电电阻定值 漏电动作时间 漏电保护跳闸投退

5.9 瓦斯保护 5.9.1 原理概述

判断井下瓦斯接点或浓度信号,作用于保护跳闸,可设定保护跳闸延时。瓦斯接点可接开动接点亦可接闭动接点,通过设置选择动作接点属性。 5.9.2 定值单及整定说明 瓦斯保护的定值单如下

定值 瓦斯投退 瓦斯接点选择 瓦斯浓度 瓦斯延时 定值范围 退/告警/跳闸 开动/闭动/频率 0.1%-3.0% 0.00s-99.99s 步长 / / 0.1% 0.01S 定值范围 退/告警/跳闸 0.0-200.0KΩ 0.00s-99.99s 告警/跳闸 步长 / 0.1KΩ 0.01S / 380V 3.5kΩ 660V 11kΩ 1140V 20kΩ 10

GCS2322数字式低压保护测控装置

5.10 风电闭锁保护 5.10.1 原理概述

判断分电闭锁接点信号,作用于风电闭锁输出,可设定解锁延时。 5.10.2 定值单及整定说明 风电闭锁保护的定值单如下

定值 风电闭锁投退 风电闭锁开入 解锁延时 定值范围 投/退 开动/闭动/主控 0.00s-99.99s 步长 / / 0.01S 当设为主控时,则本开关合闸后,经解锁延时后,风电闭锁输出接点闭合,本开关分闸后,风电闭锁输出接点立即打开。

当设为开动时,则只要保护运行,风电闭锁输出接点立即闭合。风电闭锁无开入时,立即跳闸,并分闸闭锁,直到风电闭锁有开入时,经解锁延时后解除闭锁,分闸待机。

当设为闭动时,则只要保护运行,风电闭锁输出接点立即闭合。风电闭锁有开入时,立即跳闸,并分闸闭锁,直到风电闭锁无开入时,经解锁延时后解除闭锁,分闸待机。

当设为关闭时,只要保护运行,风电闭锁输出接点立即闭合,只有保护失电时才打开。

六 试验功能

保护功能试验可择保护试验或传动试验。 1. 电流试验:

a) 包括短路、过载保护等电流回路的试验。

b) 合闸之后不做“电流试验”,因为开关合闸之后会可能有实际电流存

在,无法与试验电流区分。

2. 漏电试验:

a) 漏电试验需要接入外围试验电阻(R8)来实现。

b) 选择性漏电保护试验由外围试验电阻实现零序电流、零序电压回路及

11

GCS2322数字式低压保护测控装置

方向的测试。通常“选择性漏电保护”不做“不跳闸试验”,因为容易导致上级总开关“漏电保护”动作。

3. 试验信号的投入和退出:

保护装置在3S内判断试验信号是否符合要求,如果未检测到该信号或该信号不达到试验标准,则会提示该信号对应的试验“不正常”。试验后,屏幕会停留在试验界面,3S后保护装置将再次启动实时保护功能 4. 传动试验:

保护装置在无故障情况或不具备模拟试验的条件下,可以进行合闸传动或跳闸传动,以便检测保护的合闸回路或跳闸回路是否正常。

七 用户接线说明

1、按照本说明书的附图仅供用户参考,用户可以根据实际需要进行合理调整;

2、电流传感器为空心的电流互感器,直接穿在三相电缆出线上。需要注意一次电流从灌封面流入,而且L1、L2 接线顺序要一致——L1 分别接保护装置的IA、IB、IC、而L2 全接电流中性点In。

3、电压传感器信号由变压器提供线电压、三相相电压(额定输入保护装置的电压为10V),即变比为380/10(或者660/10、1140/10,容量0.01A),UA、UB、UC三相接线应与三相电流一一对应且极性一致。

4、瓦斯传感器由可测量瓦斯浓度的传感器输出200--1000Hz的频率,对应0--4%的瓦斯浓度,保护装置采集频率后转化为相应的瓦斯浓度,从而实现瓦斯检测及保护(瓦斯输入口是标准的频率输入接口,要求输入驱动能力为电流约10mA,电阻250 欧姆左右;输入范围200--1000Hz,对应0--4%的瓦斯浓度)。 5、键盘(按钮)共四个:“上行”、“下行”、“确定”、“复位”,也可根据用户实际需要对键盘数量进行调整。通过简单操作可随时对保护装置的保护功能进行整定,当保护装置装入隔爆型馈电开关器后,除可以通过窗口观察到显示屏上的各种信息外,通过在开关本体上的按钮也可在现场不打开开关外壳的情况下完成对保护装置的各种保护功能的整定及试验,使之真正实现保护装置的智能化。 本保护装置还带有遥控操作功能,用遥控器对保护装置进行操作,对现场调

12

GCS2322数字式低压保护测控装置

试非常方便。

6、 装置电源供电:模块的允许供电范围为70~250V,鉴于井下电网供电实际情况,对电源模块供电额定电压建议为100V/20W;

7、 ZK:组合转换开关,用于同一本体总分开关转换设置中,其中ZK-4 的触点耐压要660V;强弱电要分开布线,如ZK-1、3 与ZK-4。如果开关本体只作为总开关或只作为分开关使用,也可不用此转换开关来转换,而是按总分使用情况,直接接线。

8、 关于漏电试验,按外围图接好,可以在保护装置“保护试验”界面下操作由程序自动投入完成,其中K3 触点耐压要1300V。此外,如有必要也可以通过门上按键,人为按SB7 完成。总开关合闸后的漏电保护试验,要在系统三相电存在的情况下做。

八 人机接口系统的使用方法

本装置人机接口显示为中文显示,操作简单直观。用户在阅读完本说明书后即可以直接通过按键进行人机对话。但有几点要说明如下:

本装置具有确认、上行、下行、复位四个操作键。

“确认键”用于确认操作,如进入各级菜单、整定定值、查看事件记录等。 “上行键或下行键”用于移动光标位置或进行数值调整。“下行键”连续按下3秒钟后,将锁定当前显示内容,不在自动循环显示,此时用户可以通过“上行键”或“下行键”选择自己要查看的参数栏目。如要再次循环显示,则再次按下“下行键”3秒钟后又可以进行循环显示。

“复位键”用于对故障状态复位,故障动作后,一定要对保护复位后才能进行合闸操作,否则保护认为故障一直存在将拒绝合闸!! 8.1 实时循环显示菜单说明 国辰电气 2007-06-01 12: 18: 28 说明:显示公司名称及当前时间。

不平衡: 0% A相电流:0400A B相电流:0400A C相电流:0400A 13

GCS2322数字式低压保护测控装置

说明: 实时显示本馈电开关三相负荷电流,及三相不平衡率。

AB线电压:0660V BC线电压:0660V CA线电压:0660V 说明: 实时显示本馈电开关三相线电压。

如设置为单系统电压接入方式则无本菜单的显示。

系统电压: 0660V 有功: 744.8KW 功率因数: 0.864 电度: 99999999KWh 说明: 实时显示本馈电开关的系统电压、有功功率、功率因数和计算电度等。

分开关 零序电压: 020.9V 零序电流: 0.004mA 绝缘电阻: >200K 说明: 当设为分开关且开关在分闸状态下的显示内容。

分开关 零序电压: 020.9V 零序电流: 0.004mA 绝缘电阻: -------K 说明: 当设为分开关且开关在合闸状态下的显示内容。

总开关 绝缘电阻: >200K 说明: 当设为总开关状态下的显示内容。

14

GCS2322数字式低压保护测控装置

□□□□□□□□ 瓦斯浓度: 正常 风电闭锁: 正常 装置温度:28.8℃

说明: 实时显示本馈电开关的开关量输入情况及装置温度。菜单中的八个方框分别表示八个开关量输入状态,从左至右分别表示为瓦斯输入、远方分励、风电闭

锁、开关位置、总/分设置、备用3、备用2、备用1。

装置在交流显示菜单下,用户可以用按“下行”键在循环显示状态下进行翻

页显示。常按“下行”键3秒钟,装置即停止循环显示,停留在当前显示界面,用户可以通过按“下行”键进行翻页显示。 8.2 主菜单操作说明

装置在正常运行显示下,按“确认”键后,即显示主菜单结构,进入主菜单后,通过按“下行”键移动显示屏中的“确认”键即可进入相应的子菜单。

8.3子菜单操作说明 8.3.1保护设置菜单操作说明

到相应的子级菜单名称前,然后在按

保 护 设 置 参 数 设 置 运 行 记 录 时 间 设 置 厂 家 参 数 装 置 复 归 保 护 试 验 退 出 额定参数 短路保护 过载保护 不平衡保护 欠压保护 过压保护 漏电闭锁 选漏(分开关) 漏电(总开关) 瓦斯保护 风电闭锁 退 出 15

GCS2322数字式低压保护测控装置

装置在主菜单显示下,选择“保护设置”按“确认”键后,即显示保护设置菜单结构,进入后,通过按“下行”键移动显示屏中的称前,然后在按“确认”键即可进入相应的子菜单。

装置在定值菜单显示下,按“下行”键选择要整定的项目后,按“确认”键选中要修改的内容变为高亮,在通过按“下行”键进行修改,然后再按“确认”键对修改的内容进行保存。

到相应的子级菜单名

16

额定电压 660V 额定电流 0630A 退 出 短路保护 投入 保护方式 鉴幅 短路倍数 08倍 动作时间 00.00S 退 出 过载保护 投入 过载电流 0020A 退 出 不平衡保护 投入 不平衡系数 50% 动作时间 0001S 退 出 欠压保护 投入 欠压系数 70% 动作时间 0005S 退 出 过压保护 投入 过压系数 120% 动作时间 0005S 退 出 漏电闭锁 投入 闭锁阻值 007.0K 退 出 GCS2322数字式低压保护测控装置

选漏保护 投入 零序电压 030.0 V 零序电流 0.002mA 功率方向 投入 动作时间 00.05S 退 出 漏电保护 投入 漏电电阻 0011K 动作时间 00.05S 退 出 瓦斯保护 投入 瓦斯输入 开动 瓦斯浓度 2.000% 动作时间 05.00S 退 出

风电闭锁 投入 闭锁开入 开动 解锁延时 02.00S 退 出 8.3.2参数设置菜单操作说明 装置地址 0001 CAN 20K 485 300BPS 电压接入 单线 背光控制 15分 切屏时间 0005S 退 出

在装置与分站通信时应对装置地址进行设定。 装置地址范围均为0—254。

CAN、485波特率设定用于和分站通讯时设定通信速度。

电压接入方式设定按照实际电压接入情况进行设定,主要有三相、三相加系统电压、单系统电压三中接入方式。 8.3.3运行记录菜单操作说明

17

GCS2322数字式低压保护测控装置

保护事件记录

设备运行记录

清除事件记录

清除运行记录

清除电度记录

退 出

当前记录共04条 退出 查询

在选择保护事件记录时,会显示装置当前一共存储多少条记录,按“确认”键可进一步查询详细的保护事件记录,按“移位”键即退出保护事件查询。 64/01 短路动作 2007-06-01 3000A 12 : 28 : 58 C相 退出 查询 64/01:表示最大动态存储64条保护事件记录,当前画面显示的是第一条记录。

短路动作:表示记录的动作类型。 C相:表示动作相别

2007-06-01,12:28:58:表示当前画面发生的故障时间为2007年6月1日12点28分58秒。

动作电流:3000A:表示故障时的故障电流。 退出:按“下行”键即可退出运行记录菜单。

查询:按“确认”键即可顺序查询其他保护事件记录。

在选择运行事件记录时,会显示如下菜单内容。

运行 30000小时25分

合闸 25000小时38分

分闸 05000次

退出

运行30000小时:表示装置累计运行时间。

18

GCS2322数字式低压保护测控装置

合闸25000小时:表示开关累计运行时间。 分闸05000次:表示开关分闸次数。

在选择清除事件、运行、电度记录时,会显示如下菜单内容。

此操作将清除

所有事件记录

退出 确认

此操作将清除

所有运行记录 退出 确认 此操作将清除 所有电度记录 退出 确认

在上述菜单中,按“确认”键即会清除相应的所有存储记录,按“下行”键即取消清除相应的所有存储记录。 8.3.4时间设置菜单操作说明

07年 18时 05月 26分 07日 38秒 退出 时间设置菜单用于对时间进行设置。装置具有内部时钟记忆功能,一般不需要进行时间设置。如要进行设置可通过“下行”键和“确认”键进行操作。先通过“下行”键选择要修改的位置,然后按“确认”键,要修改的数字变亮,再按“下行”键对数字进行修改,修改好后再按“确认”键保存。 8.3.5厂家参数设置菜单操作说明

参数设置菜单主要用于对交流采样的精度进行校准,范围为0.95—1.05。此菜单为厂家使用,装置在出厂前已调整好,希望用户不要随意调整此菜单内容,以免影响保护性能!

Ia低系数 1.000 Ib低系数 1.000 Ic低系数 1.000 Io系数 1.000 Ia高系数 1.000 Ib高系数 1.000 Ic高系数 1.000 Usys系数 1.000 Ua系数 1.000 Ub系数 1.000 19

GCS2322数字式低压保护测控装置

8.3.6装置复归菜单操作说明

确认复归吗?

退出 确认

当保护动作后,保护动作画面推出后,当按“复位”键后,即出现复归菜单选择是否进行复归。当按“确认”键后,保护动作才能复归,才能进行合闸操作。当按“下行”键后,保护装置暂时退出动作画面,进入正常显示十秒钟后又将推出动作画面,要求进行复归操作。

8.3.7保护试验菜单操作说明 速断试验 漏电试验 合闸试验 分闸试验 退出 确认速断试验吗?

此操作将导致 分闸 退出 确认 确认漏电试验吗? 此操作将导致 分闸 退出 确认 确认合闸试验吗? 此操作将导致 合闸 退出 确认 确认分闸试验吗? 此操作将导致 分闸 退出 确认 由于速断和漏电试验为保护模拟试验,合闸和分闸试验为出口传动试验。这两种试验涉及到开关动作,现场在做上述试验一定要小心谨慎,确认具备试验条

20

GCS2322数字式低压保护测控装置

件后再进行试验操作!!!

九.各部件安装尺寸

9.1 电流互感器安装尺寸

521044R190507171,5470309.2 零序电流互感器安装尺寸

21

GCS2322数字式低压保护测控装置

R68R37,513623

9.3 保护装置安装尺寸

22

GCS2322数字式低压保护测控装置

2613826512267021251263R10391910019138图面正图面正23

GCS2322数字式低压保护测控装置

十.保护装置清单表

序号 1 2 3 名称 数字式保护测控装置 电流互感器 零序电流互感器 型号 GCS2322 LH1 LHO 数量 1只 3只 1只 注:若客户有需要,可选购 零序电抗器、660V/40V变压器、三相电抗器/三相(电抗+同步)变压器660/10V。

24

21-模拟量输入+22-模拟量输入-23-空24-电流中性点25-C相电流26-B相电流27-A相电流28-零序电流29-电压中性点30-零序电压31-C相电压32-B相电压33-A相电压34-系统电压35-大地36-漏电输入37-模拟量输出+38-模拟量输出-

2A345678电源合闸运行跳闸十

1A一

B通信动作BGCS2322数字式低压保护测控装置南京国辰电气控制有限公司典型

CC接

D1-瓦斯浓度+2-瓦斯浓度-3-备用14-备用25-备用36-总/分设置风电闭锁-39故障时开-40合闸-41输出-42试验- 43输出2-44D线

GCS2322数字式低压保护测控装置原

EE理

7-开关位置8-风电闭锁9-远方分励10-瓦斯输入11-复位12-确认13-下行14-上行15-CANL16-CANH17-GNDC18-RS485A19-RS485B20-公共端试验- 45输出1-46保护输出-47故障时开-48保护输出-49故障时闭-50备用常开-51备用常闭-52公共端-53ROUT5-54ROUT6-55空-56AC75-265N-57AC75-265L-58GCS2322数字式低压保护测控装置姓设校批日装置印字图 GCS2322数字式低压保护测控装置

25

23F456南京国辰电气控制有限公司78F1

2345678A

C21-模拟量输入+22-模拟量输入-23-空24-电流中性点25-C相电流26-B相电流27-A相电流28-零序电流29-电压中性点30-零序电压31-C相电压32-B相电压33-A相电压34-系统电压35-大地36-漏电输入37-模拟量输出+38-模拟量输出-26

分开关总开关1A瓦斯检测仪ZK-1QF-11-瓦斯浓度+2-瓦斯浓度-3-备用14-备用25-备用36-总/分设置7-开关位置风电闭锁-39故障时开-40合闸-41输出-42试验- 43输出2-44试验- 45BGCS2322数字式低压保护测控装置K2-1合闸线圈SB6SB5SB4SB3K2-2BGCS2322综保装置K18-风电闭锁9-远方分励10-瓦斯输入11-复位12-确认13-下行14-上行15-CANL16-CANH17-GNDC18-RS485A19-RS485B20-公共端输出1-46保护输出-47故障时开-48保护输出-49故障时闭-50备用常开-51备用常闭-52公共端-53ROUT5-54ROUT6-55空-56AC75-265N-57AC75-265L-5844K348BH47失压脱扣4349BH50KT-1K2CSB1K1-1分励脱扣QF2ZK-2分开关分开关总开关100V30W10V0.5W42HZ41KTSB250V127V36VD2V2WT345SY1140V,660V/40V(0.5W)T4总开关ZK-346T2DT5T1(L1)1140V,660V/10V(相)0.5WC1ZK-3QF说明:R1:10K/10WR2:7K/20WC1:2uF/630VC2:10uF/100VABCER2总开关QF-3分开关SB7K3-1R1GCS2322数字式低压保护测控装置

E虚框内接线仅供参考GCS2322数字式低压保护测控装置姓名设计校对批准日期接线原理图南京国辰电气控制有限公司FC2F23456178